www.megger.comEVX1008Overview3. Overview3.1 EVX100 layout12ItemDescription1 Battery level check button2 LED indicator3.2 EVSE (Charger) Status codesThe following list explains the EV charger status codes reported by the MFT-X1 when using the EVX100. Most of these codes will only appear momentarily during a tripping test sequence. For normal operation with the MFT-X1 switched on and the EVX100 connected to a working charger the EV charger will be in state C2.Status CodeDescriptionAction requiredEVSEEVX100 not connected to Charger or Charger not detected.Check utility supply to Charger.A1/A2 Charger not ready.Displayed when the EVX100 is cycling through A/B/C codes to reset charger after tripping test.B1EVX detected.Charger not ready to suppply energy. B2EVX detected.Charger ready to supply energy (connector interlock should be engaged).Displayed during RCD or RDC trip automatic resetting sequence.C1EVX comms established with charger. Green EVX flashing light.Charger not ready to supply energy.Rare - this is normally a fault condition of the charger. The EVX100 cannot set the charger into C2 charging active mode.C2EVX connected and active - Charger output active.This is the normal operating state before any tripping test is applied.EError state. Usually loss of utility power. Also possible loss of utility supply.Charge EVX100 and MFT-X1. Check utility supply before restesting.FFault. Usually generated during a CP or PE error state.