8. Proximity Pilot – PP-Status With the EVCA210 adaptor connected to the charging point, use the PP State rotary switch to simulate any of the listed current capabilities of a charging cable. Selection of cable current capabilityNC (No Cable)13 A20 A32 A63 ANote: The EVCA210 does load the circuit but will not draw significant current for this measurement.9. Control Pilot – CP State With the EVCA210 adaptor connected to the charging point, use the CP State rotary switch to select different simulated vehicle states. Selection of Vehicle State Vehicle StateAElectric vehicle not connectedBElectric vehicle connected, not ready to chargeCElectric vehicle connected – ready to charge (ventilation not required)DElectric vehicle connected – ready to charge, (ventilation required)4 mm CP Signal output ports are located on the top of the EVCA210.These terminals are connected to the CP and PE conductors of the charging point. The green 4mm terminal is connected to PE. For details of the communication protocol please refer to IEC 61851-1 and any documentation provided by the manufacturer of the charging point under test.CP Error “E” With the CP state set to either C or D (EV connected and ready to charge) and the PP state set to any setting except NC, by pressing the CP Error “E” button, a CP error is safely simulated. The pending charging process should stop immediately and new charging processes prevented.www.megger.comEVCA210 11Proximity Pilot – PP-Status
Previous page: EVCA210 laddpunktsadapter för elfordon [10 / 16]