Line SeriesCanalis KB 25 and 40 ACatalogue 06-2023Prefabricated busbar trunking for lighting and power distributionse.com
CO2 and P&L impact through... Resource PerformanceGreen Premium brings improved resource efficiency throughout an asset’s lifecycle. This includes efficient use of energy and natural resources, along with the minimization of CO2 emissions.Cost of ownership optimization through... Circular PerformanceWe’re helping our customers optimize the total cost of ownership of their assets. To do this, we provide IoT-enabled solutions, as well as upgrade, repair, retrofit, and remanufacture services.Peace of mind through... Well-being PerformanceGreen Premium products are RoHS and REACh compliant. We’re going beyond regulatory compliance with step-by-step substitution of certain materials and substances from our products.Improved sales through... DifferentiationGreen Premium delivers strong value propositions through third-party labels and services. By collaborating with third-party organizations we can support our customers in meeting their sustainability goals such as green building certifications.The Green Premium program stands for our commitment to deliver customer valued sustainable performance. It has been upgraded with recognized environmental claims and extended to cover all offers including Products, Services and Solutions.Discover what we mean by greenCheck your products!An industry leading portfolio of offers delivering sustainable valueGreen PremiumTMMore than 75% of our product sales offer superior transparency on the material content, regulatory information and environmental impact of our products:• RoHS compliance• REACh substance information• Industry leading # of PEP’s*• Circularity instructions*PEP: Product Environmental Profile (i.e. Environmental Product Declaration)
3ABCDEFGCanalis KB 25 and 40 APresentation 4Description 16Catalogue numbers 23Dimensions 40Design guide 44Applications 54Index 64www.se.com
4www.se.comA new path for achieving your electrical installations Canalis is part of a comprehensive offer of products that are perfectly coordinated to meet all medium and low voltage electrical distribution requirements. All of these products have been designed to work together: electrical, mechanical and communication compatibility. The electrical installation is thus both optimised and high-performance.Optimum system performance is ensured by coordination between the protection circuit breakers and the busbar trunking used for decentralised distribution.Decentralised electrical distribution with total coordination perfectly satisfies all your requirements in terms of safety, continuity of service, upgradeability and simplicity.Decentralised electrical distribution with total coordination is the ideal solution for a wide range of applications including factories, warehouses, commercial premises, parkings, etc.PresentationCanalis, a comprehensive and consistent busbar trunking system for...
5www.se.comAEasier• CoordinationSchneider Electric pro poses coordinated busbar trunking and circuit breaker combinations for all your applications.For typical applications with power ratings up to 630 kVA, a solution in cluding the low-voltage electrical switchboard, circuit breakers and Canalis busbar trunking en sures an installation sized to handle all short-circuit levels encountered.• DesignThe electrical installation can be designed without knowing the exact loca tion of the equipment to be supplied.• OperationCanalis opens the door to total upgradeability throughout the installation.Connectors with stand ard performance circuit breakers can be in stalled at any point along the busbar trunking run.Safer• Decentralised distribution system The combination of cas cading and discrimination techniques guarantees optimum safety and continuity of service.• DesignTotal discrimination for enhanced protection as standard and at a lower cost.point de la canalisation.• OperationAny changes to your installation are carried out in complete safety.Connectors can be plugged in and out with the trunking live. They are equipped with interlocking systems to pre vent incorrect mounting.Coordination guarantees their installation at any point on the busbar trunking system.Presentation... lighting and power distribution in all types of buildings
6www.se.comPresentationPanorama of Canalis rangePB115580-30Horizontal and vertical distribution from 100 to 1000 A - IP55IncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKS *Aluminium: Copper:690 VPre-lacquered white (RAL9001)3 m, 5 m and additional or customized components4 + PE0.5 m or 1 m on each side for horizontal version, and on one side for vertical version16 A to 400 A (plug-in)Units for circuit breakers (modular, Compact NSX), fuses, sockets> Riser ducting offer> Fixing devices with quick adjustment> Cable ducts> Installation accessories> Fire barriers100 A, 160 A, 250 A, 400 A, 500 A, 630 A, 800 A, 1000 A160 A, 250 A, 400 A, 630 A, 800 A* Canalis KS range is available on se.com or catalogue: DEBU026ENPD202221_r KNPower distribution from 40 to 160 A - IP55IncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKN *40 A63 A100 A160 A500 VPre-lacquered white (RAL9001)2 m and 3 m4 + PE0.5 m, 1 m on 1 side16 A to 63 A (plug-in)Units for modular circuit breakers, fuses and sockets> Flexible components > Fixing devices with quick adjustment> Remote control bus > Cable ducts> Installation accessories* Canalis KN range is available on se.comPD202088-74_rPower transmission and distribution from 800 to 6300 A - IP55IncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKT *Aluminium: Copper:1000 VPre-lacquered white (RAL9001)2 m and 4 m3P + PE 3P + N + PE 3P + N + PER0.5 m or 1 m25 A to 630 A (plug-in)400 A to 1250 A (bolt-on)Units for circuit breakers (modular, Compact NSX), fuses, sockets> Power supply ends > Direction change angles and T-pieces> Fixing devices and fuses800 A, 1000 A, 1250 A, 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A1000 A, 1350 A, 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A, 6300 A* Canalis KT range is available on se.com or catalogue:KTA: ref. DEBU021EN / KTC: ref. DEBU024ENDB410226Power transmission for outdoor and harsh environment from 800 to 6300 A - IP68IncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKR *800 A, 1000 A, 1250 A, 1350 A , 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A, 6300 A1000 VGray (RAL7030)Up to 3 m3L3L + N or 3L + PE or 3L + PEN 3L + N + PE---> Power supply ends > Direction change angles and T-pieces> Fixing devices > Fire resistant elements* Canalis KR range is available on se.com or catalogue ref. DEBU031ENPB122259Lighting and low power distribution from 25 to 40 A - IP55Rated service currentRated insulation voltageColorLine componentsBranching pointsAccessoriesIncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKBA25 A40 A690 VPre-lacquered white (RAL9003)2 m and 3 m2 or 4 + PE0.5 m, 1 m on 1 sideL + N + PE or3L + N + PE (10/16 A)pre-cabled or to be cabled,with phase selection or fixed polarity, with lighting control With fuses or without protection> Flexible components > Fixing devices with quick adjustment > Communication bus (DALI, KNX, ASI)> Cable ductsKBB25 A40 A690 VPre-lacquered white (RAL9003)2 m and 3 mSingle circuit2 or 4 + PEDual circuit2 + 2 + PE2 + 4 + PE4 + 4 + PE0.5 m or 1 m on 1 or 2 sidesL + N + PE or3L + N + PE (10/16 A) pre-cabled or to be cabled,with phase selection or fixed polarity, with lighting control With fuses or without protection> Flexible components > Fixing devices with quick adjustment> Communication bus (DALI, KNX, ASI)> Cable ducts
7www.se.comAPresentationPanorama of Canalis rangeHorizontal and vertical distribution from 100 to 1000 A - IP55IncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKS *Aluminium: Copper:690 VPre-lacquered white (RAL9001)3 m, 5 m and additional or customized components4 + PE0.5 m or 1 m on each side for horizontal version, and on one side for vertical version16 A to 400 A (plug-in)Units for circuit breakers (modular, Compact NSX), fuses, sockets> Riser ducting offer> Fixing devices with quick adjustment> Cable ducts> Installation accessories> Fire barriers100 A, 160 A, 250 A, 400 A, 500 A, 630 A, 800 A, 1000 A160 A, 250 A, 400 A, 630 A, 800 A* Canalis KS range is available on se.com or catalogue: DEBU026ENPower distribution from 40 to 160 A - IP55IncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKN *40 A63 A100 A160 A500 VPre-lacquered white (RAL9001)2 m and 3 m4 + PE0.5 m, 1 m on 1 side16 A to 63 A (plug-in)Units for modular circuit breakers, fuses and sockets> Flexible components > Fixing devices with quick adjustment> Remote control bus > Cable ducts> Installation accessories* Canalis KN range is available on se.comPower transmission and distribution from 800 to 6300 A - IP55IncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKT *Aluminium: Copper:1000 VPre-lacquered white (RAL9001)2 m and 4 m3P + PE 3P + N + PE 3P + N + PER0.5 m or 1 m25 A to 630 A (plug-in)400 A to 1250 A (bolt-on)Units for circuit breakers (modular, Compact NSX), fuses, sockets> Power supply ends > Direction change angles and T-pieces> Fixing devices and fuses800 A, 1000 A, 1250 A, 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A1000 A, 1350 A, 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A, 6300 A* Canalis KT range is available on se.com or catalogue:KTA: ref. DEBU021EN / KTC: ref. DEBU024ENPower transmission for outdoor and harsh environment from 800 to 6300 A - IP68IncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKR *800 A, 1000 A, 1250 A, 1350 A , 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A, 6300 A1000 VGray (RAL7030)Up to 3 m3L3L + N or 3L + PE or 3L + PEN 3L + N + PE---> Power supply ends > Direction change angles and T-pieces> Fixing devices > Fire resistant elements* Canalis KR range is available on se.com or catalogue ref. DEBU031ENLighting and low power distribution from 25 to 40 A - IP55Rated service currentRated insulation voltageColorLine componentsBranching pointsAccessoriesIncUiLength ofcomponentsNumber of conductorsCenter to center distanceProtection typeKBA25 A40 A690 VPre-lacquered white (RAL9003)2 m and 3 m2 or 4 + PE0.5 m, 1 m on 1 sideL + N + PE or3L + N + PE (10/16 A)pre-cabled or to be cabled,with phase selection or fixed polarity, with lighting control With fuses or without protection> Flexible components > Fixing devices with quick adjustment > Communication bus (DALI, KNX, ASI)> Cable ductsKBB25 A40 A690 VPre-lacquered white (RAL9003)2 m and 3 mSingle circuit2 or 4 + PEDual circuit2 + 2 + PE2 + 4 + PE4 + 4 + PE0.5 m or 1 m on 1 or 2 sidesL + N + PE or3L + N + PE (10/16 A) pre-cabled or to be cabled,with phase selection or fixed polarity, with lighting control With fuses or without protection> Flexible components > Fixing devices with quick adjustment> Communication bus (DALI, KNX, ASI)> Cable ducts
8www.se.comPresentationCanalis KB is a simple and economical solution for lighting and low power distribution Lighting management is an essential means of providing users with greater comfort, whilst at the same time reducing their energy bill. An affordable, easily-implementable solution for medium-sized tertiary buildings and workshops is available: Canalis in combination with DALI or KNX protocols20% 35% Achievable savings thanks to energy management Lighting share of a building’s electricity consumptionGreater comfort for users Lighting management makes it possible to compensate for light variations due to weather and sunlight by creating a uniform luminous flux. A well-lit workstation has a direct impact on the well-being of the employees and the quality of their work, as well as on their safety. • Offices• Workshops• Car parks• Supermarkets• Logistics centers• Data-centersAnd better energy efficiencyControlling lighting by zone, creating lighting scenarios on the basis of occupancy time, switching off lights in unoccupied zones, etc. Lighting management optimises the use of equipment to significantly reduce electricity consumption.
9www.se.comAEasy to installThe compact nature of Canalis makes it easy to integrate in all parts of the building.Since it is based on a decentralized architecture, Canalis can be installed at the same time as the building is being built, which optimizes site construction schedules.Because of the delayed differentiation linked to the Canalis architecture, new constraints can be taken into account without adding to the installation time. The Canalis ranges are factory-tested, which ensures a very high level of quality on site and considerably improves the success of site acceptance tests.Practical to recycleOver the last 20 years, recycling has become a major challenge for industry. The composition of Canalis ranges guarantees a 95% recycling rate.But the Canalis offers go one better... if a site is being restructured or enlarged, the products can simply be removed and reinstalled in their new environment.Simple to maintain No maintenance is required on the Canalis electrical contacts. The clarity of the Canalis architecture simplifies building maintenance and upgrades: > enlarging office space, > adding check-outs in a supermarket... Decentralized distribution ensures continuity of service; when associated with a 100% maintained or non-maintained supply, the essential functions are guaranteed: > maintaining the cold chain in a hypermarket, > lighting system in a car park...Simple to estimateSimple to maintainPractical to recycleEasy to installSimple to estimateDesigning Canalis installations is straightforward as there is no need to know the exact location, nor the power rating of the loads to be supplied. It is therefore very quick to cost the distribution functions. Moreover, Canalis’s flexibility means you can invest in existing needs without adversely affecting future expansion.Power distribution is a major challenge in the construction and refurbishment of commercial, industrial buildings and data centers.The choice of device is fundamental as it will have an effect on the building’s lifecycle. Infrastructures must comply with existing requirements while being flexible, networked and smart. The Canalis concept is undoubtedly the best solution to meet the needs of today and the challenges of tomorrow.PresentationProduct lifecycle
10www.se.comDownload a wide selection of Cahiers Techniques from www.se.comIn cruise ships >DESWED105014ENIn livestock production buildings >DESWED105010ENIn logistic centres >DESWED105011ENAutomotive industry guide >KD0C98CTAAUENIn car parks >DESWED108011ENIn greenhouses >DESWED105013ENIn garages >DESWED106004ENHypermarkets guide >KD0C98CTAHYENApplication sheets/Technical guidesQuotation and Design toolsPresentationCanalis tools and servicesiBusway for Data Center catalogue >DEBU028ENiBusway for Data Center brochure >DEBU027ENSolution for Data CenteriBusway for lighting management: Canalis-DALI technical installation guide >DEBU032ENiBusway for lighting management brochure >DESWED112002ENLighting technical guide >A9GT15ELED Lighting technical guide >CA909008EiBusway for Lighting management Canalis - DALI technical and installation guideSolution for lighting managementCanBrass >is a design and costing tool for Canalis busbar trunking runs.CanCad >is a Plug-in for Autocad. It allows to easily design and get bill of materials.BIMBusway >is a Plug-in for Revit. It allows to easily design and get bill of materials in BIM format.
11www.se.comA
12www.se.comPresentationCanalis KB is a fast and easy mounting solutionEasy to extendTool-free112Click!2Click!12
13www.se.comFlexible installationTool-freePresentationCanalis KB is a safe and robust solutionAll components in the KBA range are halogen free.In case of fire, Canalis KBA does not release smoke or toxic gases.No toxic emission in case of fireCanalis KB trunking forms a rigid beam, even at the junction between two lengths.Its facilitates the alignment of the luminaires.Very rigidRated current 25 A or 40 A.Rated Operational voltal 230 or 400 V.IP 55.IK 06.Color White RAL9003.Compliant with protocols DALI and KNX.Main characteristicsClick!IP55 guarantees trunking protection against splashes and dust.Canalis KB complies with sprinkler tests, guaranteering operation under vertically and horizontally sprayed water for 50 minutes.The high degree of protection for Canalis KB means it can be installed in all types of buildings.A high degree of protectionA
14www.se.comPresentationCanalis KB is a comprehensive solution2. Feed units and end covers bThe feed units delivred with the end covery receive the cables supplying one end of Canalis KB trunkings.1. Run components bRating: 25 or 40 A. b2 or 4 live conductors. bBasic lengths: 2 and 3 metres.Canalis KBACanalis KBBCanalis KBACanalis KBB463046461 circuit1 or 2 circuitsReinforced mechanical structure12334
15www.se.com1334444433. Fixing system and cable trays bThe fixing system ensures that Canalis KB is well secured, whatever the type of building structure. There are also fixings to secure the luminaires to Canalis KB. bA metal duct is available for running other circuits such as emergency lighting, low-current circuits, etc.4. Connectors bThe 10 and 16 A connector pre-wired or not, offer phase selection or fixed polarities, and can be used on KBA and KBB ranges.A
16www.se.comStraight lengths constitute the basic structure of the line and are made up of:1 an all-in-one carrier casing, crimp closed, forming a rigid beam made of sheet steel, in RAL 9003 white lacquered sheet steel, hot galvanised on both sides. This casing also acts as the protective earth conductor (PE),2 a ribbon cable with two or four copper conductors, 3 one, two, three or five connector outlets,4 an electrical jointing unit ensuring automatic and simultaneous connection of all live conductors,5 a mechanical joining device made of galvanised sheet steel that makes the connection of two lengths rigid and resistant to bending. The degree of protection is IP55 (without accessories).The busbar trunking is non-flame-propagating as per the recommendations of standard IEC 60332-3. All the insulating and plastic materials are halogen-free and have enhanced fire-withstand capabilities (incandescent wire test as per standard IEC 60695-2). b960°C for components in contact with live parts. b650°C for other components.Multi-circuit possibilitiesThe many possibilities offered by KBB trunking means specialised circuits can be created, e.g. for emergency lighting, presence detection, dimming.One circuitTwo circuitsStandard offer without bus L1NPEL2L1L3NPEPEL1NL1NL2L1L3NL1NPEL2L1L3NL2L1L3NPEStandard offer DALI bus is made by using two regular conductorsDali +Dali -LNPEL2L1L3NDali +Dali -PEStandard offer with internal shielded bus and dedicated connectors supporting KNX protocol. DALI bus is made by using two regular conductorsKNXDALI +DALI - LNPEL2L1L3NDALI +DALI - PEKNXStandard offer with internal shielded bus and dedicated connectors supporting DALI, KNX or other protocols L1NPEBUSBUSL2L1L3NPEPEL1NL1NBUSL2L1L3NL1NPEBUSL2L1L3NL2L1L3NPEBUS L2L1L3NL2L1L3NPEBUS = Canalis KBBDescriptionStraight lenghts
17www.se.comDescriptionFixing bracketsFor attachment of the busbar trunking to the structure of the building, either directly or via a threaded rod, chain or steel cable (the latter two with a pigtail hook or a closed ring). bDesigned to relieve the installer of the weight of the busbar trunking once placed in a bracket. bAutomatic locking of moving part on closing (unlocking requires a tool). bThe maximum recommended fixing distance is: 3 metres.1 Universal fixing bracket KBA40ZFU or KBB40ZFU For suspension on a threaded rod, diameter 6 mm. For horizontal mounting on a beam, pendant, wall, etc.2 Cable suspension system KBA40ZFSU or KBB40ZFSU Cuts mounting time of the fixing system to one-third of that required for threaded rods. Enables height adjustment of the trunking.3 Adjustable, threaded-rod suspension system KBB40ZFPU For suspension on a threaded rod, diameter 6 mm. A spring system locks the threaded rod in position for fast adjustment of the trunking.4 Pigtail hook KBB40ZFC For suspension by a chain.5 Closed ring KBB40ZFC6 Mounted on the luminaire for suspension.6 Raiser KBB40ZFMP For mounting on wall or false floor.7 Open hook KBB40ZFC5 To suspend the luminaire.213457518756161LuminairesAttached to the luminaires before mounting, these fixings ensure fast and direct fixing to Canalis KB. bSame catalogue numbers as the busbar fixings. bAutomatic locking of moving part on closing. bUse with an open hook and/or closed ring enables suspension.8 Double universal fixing bracket KBA40ZFU2W or KBB40ZFU2W for heavy luminaires.Cable supportFor running adjacent circuits such as emergency lighting, low-current circuits, etc.1 Cable brackets KBB40ZFGU Clips to trunking for fast mounting. It is possible to run three cables (diameter 5 to 16 mm) and two IRL tubes.2 Cable duct KFB25CD253 The cable duct fits on support KBB40ZFG1, which in turn fits onto a threaded rod suspension system KBA40ZFPU. An intermediate support is placed between the duct and the trunking if the distance between the suspension points exceeds 2 metres. Each duct is equipped with a connection device.OptionsEmpty length (no electric circuit)Used to adjust line length to building dimensions (e.g. to reach a fixing point).Two metres long, can be cut on site.KBA40EDA20W or KBB40EDA20W.B
18www.se.comDescriptionConnectorsConnectors (general)L1 + NL2 + NL3 + NKBC10DCS101KBC10DCS201KBC10DCS301For instantaneous connection of luminaires to busbar trunking: bthey can be handled while energised and under live conditions bthe contacts for live conductors are of the clamp type bPE connection occurs before that of the phases and neutral bphase-selection system (clip-in contact studs) for balancing of 3-phase distribution systems bselection is visible via a transparent window ba coloured lock holds them in the connector outlet ball the insulating and plastic materials have a high fire-retardant capacity: vincandescent-wire test in compliance with IEC 60695-2: - 960°C for components in contact with live parts, - 650°C for other components.All the insulators and plastic components are halogen free.Connectors 10 A direct pre-wired - 0.8 mPre-wired with SO5Z1Z1-F 3 x 1.5 mm2 cable, 0.80 m long, pre-stripped on luminaire end: b10 A rating bfixed L + N + PE polarity bthe various models make it possible to balance 3-phase distribution systems.The colour of the lock and the casing enable remote identification of the polarity.1 Live-conductor contacts.2 Protective-conductor contact.3 Lock.Connectors 10 A direct with phase selectionKBC10DCBpp bThe two contact studs are movable and can be used to set up both L + N + PE and 2L + PE distribution. bSupplied complete with a cable gland.KBC10DCC211Pre-wiredType DCC bPre-wired with SO5Z1Z1-F 3 x 1.5 mm2 cable, 1 m long, pre-stripped on luminaire end. bIf prefabricated leads are used, the line must have 16 A protection (see possibilities of dispensing with protection in the simplified design guide for lighting distribution, in the section on protection against overloads).To be wiredType DCB bTo be wired for connection of luminaires using a cable of specific type, size or length. bFast connection for 3 x 0.75 to 1.5 mm2 cable. If prefabricated leads are used, the line must have 16 A protection (see possibilities of dispensing with protection in the simplified design guide for lighting distribution, in the section on protection against overloads).Identification of the selected phase
19www.se.comConnectors 16 A with phase selection not wiredKBC16DCBppKBC16DCFppKBC16DCPpp bPhase selection: L+N or 2L (mobile studs) bTerminal connections for 0.75 to 1.5 mm2 cable. bSupplied with a cable bushing. bInstallation is facilitated by the side guides. bExist with 3L+N or with fixed polarity as well.Without protectionType DCBFor direct connection of luminaires using a specific cable.Can be equipped with the accessory to connect the remote-control circuit to theluminaires.For protection with fuses (not provided)Type DCFFor cylindrical fuse NF 8.5 x 31.5 (not supplied), 16 A gG maximum, breakingcapacity 20 kA.Type DCPWith cylindrical fuse NF 8.5 x 31.5 (supplied), 16 A gG maximum, breakingcapacity 20 kA.Supplied with power socket NF or VDE standard - 2P+T 10/16 A, 250 V.Interlocking deviceRed interlocking deviceFor all 10 A and 16 A connectors.A set of three interlocking devices in different colours can be used to mechanicallylock out connector when two or three different distribution networks are present(load, voltage, frequency, etc.). KBC16ZL10, KBC16ZL20 or KBC16ZL30. bAn interlocking device is made up of a handle and an interlocking device on each end. It can be used for an outlet and the corresponding connector. bInterlocking devices are supplied with labels that can be placed on the connector and the trunking for identification.AccessoriesKBC16ZC1Rear support bracket KBC16ZC1Additional fixing of KBC16 connector using the rear support bracket may be necessary, notably if there is a risk of accidental pulling on the cable or if the cable is very heavy (great length).KBC16ZB1Outlet blanking plate KBC16ZB1Spare part intended to restore IP55 on an outlet following removal of the connector (if original blanking plate is lost).Description ConnectorsB
20www.se.comFor DALI protocol onlyDali +Dali -LNPE L2L1L3NDali +Dali -PEAre Can beKBC10DCB40Dali +Dali -LNPEKBC16DCBp0KBC10DCSp01KBC10DCS101L2L1L3NDali +Dali -PEKBC10DCC211Straight lengthsTwo of the conductors are dedicated to the communication bus.ConnectorsThe connector is common for both power and communication.Connectors can be equipped with two cables. One to feed the power and one green for the control of the device.A lock system avoid connection to the non proper line.Bus characteristicsDALIUnitValuesCross-section and type of conductormm22 x 2.5 copperRated insulation voltage (Ui) (between power circuit and bus)V690Rated operational voltage (Ue) (max. U between bus + and - poles) V230 to 400Maximum operational current (Ie)A25Linear resistance mΩ/m52Linear capacitance pF/m30Maximum recommended lengthm300For combined DALI and KNX protocols KNXDALI +DALI - LNPE L2L1L3NDALI +DALI - PEKNXKBC16ZT1KBC16DCp40+KNXDALI +DALI - LNPEKBC10DCS101L2L1L3NDALI +DALI - PEKNXKBC16ZT1KBC16DCp40+Straight lengthsA internal sheilded decated bus is use to connect KNX devices. This bus isa KNX certified bus.2 conductors are dedictated to the communication DALI. Only proper connectors can be installed.ConnectorsConnectors are common for both power and communication. Alow with the same connector to feed power to luminaires and A lock system avoid to connect it on a non proper line.Bus characteristicsSee DALI and KNX bus characteristics.DescriptionControl system3 possible solutions
21www.se.comFor KNX protocol alone or other protocols needing a shielded busL1NPEBUSBUSL2L1L3NPEPEL1NL1NBUSL2L1L3NL1NPEBUSL2L1L3NL2L1L3NPEBUS L2L1L3NL2L1L3NPEBUSL1 + NBUS +/-L2 + NBUS +/-L3 + NBUS +/-KBC16DCS101TKBC16DCS201TKBC16DCS301TL1L3L2NPE1234BUS +/-Straight lengthsA internal shielded decated bus is use to connect KNX devices. This bus is a KNX certified bus.ConnectorsConnectors are common for both power and communication. Alow with the same connector to feed power to luminaires and a lock system avoid to connect it on a non proper line.The colour of the lock and the casing enable remote identification of the polarity.1 Live-conductor contacts.2 Bus conductor contacts.3 Bus cable.4 Lock.Bus characteristicsKNXUnitValuesCross-section and type of conductormm22 x 0.5 copperRated insulation voltage (Ui) (between power circuit and bus)V500Rated operational voltage (Ue) (max. U between bus + and - poles) V32Maximum operational current (Ie)A3.8Linear resistance mΩ/m75Linear capacitance pF/m100Maximum KNX recommended lengthm30016 A for circuit breaker and fusesConnection of the remote-control receiver using a KBC16DCB, KBC16DCF or KBC16DCP connector equipped with a KBC16ZT1 contact-block accessory delivered with cable gland.Feed units equipped with an additional bus terminal block. Connectors are equipped with two cables. One for the devices power and for the control the device.KBC16DCp22KBC16DCPpKBC16DCp21KBC16DCp40+==KBC16ZT1with cable glandDescription Control system3 possible solutionsB
22www.se.comDescriptionThe offer is organised in 3 chaptersThe essentialsOnly 4 references to simplify and faster your choiceClassic offerFor usual lighting or power distribution without communication busControl systemFor lighting or any other devices controlled with DALI or KNX protocols
23www.se.comCatalogue numbersThe essentialsOnly 4 referencesL2L1L3NPE25 AED - Straight lengthKBA25ED4303WType of componentLength (m)Number of outletsCatalogue numbersOrder in multiples of 6Distribution length33KBA25ED4303WAB - Feed unitKBA25ABG4WMountingTerminals (mm²)Cable gland max Ø (mm)Catalogue numbersOrder in multiples of 1Left4PG16 Ø15KBA25ABG4WZF - Fixing bracketKBA40ZFUType of componentMountingCatalogue numbersOrder in multiples of 10Universal fixing bracketSuspended on threaded rod or lateral (except wall)KBA40ZFUDCB - Connector direct not wired 10 A with phase selectionKBC10DCB20PolaritySchemeCatalogue numbersOrder in multiples of 10L1 + N orL2 + N orL3 + NPEL3L1L2NKBC10DCB20C
24www.se.comCatalogue numbersClassic offerLine componentsL1NPEL2L1L3NPEPEL1NL1NL2L1L3NL1NPEL2L1L3NL2L1L3NPE25 A40 A25 A40 A25 A40 A25 A40 A25 A40 AED - Straight lengthsKBA●●ED●●●●●WKBB●●ED●●●●●WLength (m)Distance between outlets (m)Number of outletsCatalogue numbersOrder in multiples of 6Catalogue numbersOrder in multiples of 630.55KBA25ED2305WKBA40ED2305WKBA25ED4305WKBA40ED4305WKBB25ED22305WKBB40ED22305WKBB25ED42305WKBB40ED42305WKBB25ED44305WKBB40ED44305W13KBA25ED2303WKBA40ED2303WKBA25ED4303WKBA40ED4303WKBB25ED22303WKBB40ED22303W----1.52KBA25ED2302W-KBA25ED4302W--------0KBA25ED2300WKBA40ED2300WKBA25ED4300WKBA40ED4300WKBB25ED22300WKBB40ED22300WKBB25ED42300WKBB40ED42300WKBB25ED44300WKBB40ED44300W20.53KBA40ED2203WKBA40ED2203WKBA40ED4203WKBA40ED4203WKBB40ED22203WKBB40ED22203WKBB40ED42203WKBB40ED42203WKBB40ED44203WKBB40ED44203W12--KBA25ED4202W-------AB - Feed unitsKBA25ABG4WMountingTerminals (mm²)Cable gland max Ø (mm)Catalogue numbersOrder in multiples of 1Catalogue numbersOrder in multiples of 1Left4PG16 Ø15KBA25ABG4W-KBA25ABG4W-------KBB40ABG44WKBA40ABG4WLeft10PG21 Ø19KBA40ABG4WKBA40ABG4WKBA40ABG4WKBA40ABG4WKBB40ABG44WKBB40ABG44WKBB40ABG44WKBB40ABG44WKBB40ABG44WKBB40ABG44WKBA40ABD4WRight10PG21 Ø19KBA40ABD4WKBA40ABD4WKBA40ABD4WKBA40ABD4W------KBB40ABT44WKBA40ABT4WCentral10PG21 Ø19KBA40ABT4WKBA40ABT4WKBA40ABT4WKBA40ABT4WKBB40ABT44WKBB40ABT44WKBB40ABT44WKBB40ABT44WKBB40ABT44WKBB40ABT44WDF - Flexibles KBB40DF420W- KBB40DF4420WKBB40DF405W - KBB40DF4405WKBA40DF420WKBA40DF405WType of componentLength (m)Catalogue numbersOrder in multiples of 1Catalogue numbersOrder in multiples of 1Flexible0.5KBA40DF405WKBA40DF405WKBA40DF405WKBA40DF405WKBB40DF405WKBB40DF405WKBB40DF4405WKBB40DF4405WKBB40DF4405WKBB40DF4405W2KBA40DF420WKBA40DF420WKBA40DF420WKBA40DF420WKBB40DF420WKBB40DF420WKBB40DF4420WKBB40DF4420WKBB40DF4420WKBB40DF4420WZF - Fixing bracketsKBA40ZFUKBB40ZFUType of componentMountingCatalogue numbersOrder in multiples of 10Catalogue numbersOrder in multiples of 10Universal fixing bracketSuspended on threaded rod or lateral (except wall)KBA40ZFUKBA40ZFUKBA40ZFUKBA40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBA40ZFSUKBB40ZFSUCable suspension systemWith 3 m steel cableKBA40ZFSUKBA40ZFSUKBA40ZFSUKBA40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSU
25www.se.comL1NPEL2L1L3NPEPEL1NL1NL2L1L3NL1NPEL2L1L3NL2L1L3NPE25 A40 A25 A40 A25 A40 A25 A40 A25 A40 AED - Straight lengthsKBA●●ED●●●●●WKBB●●ED●●●●●WLength (m)Distance between outlets (m)Number of outletsCatalogue numbersOrder in multiples of 6Catalogue numbersOrder in multiples of 630.55KBA25ED2305WKBA40ED2305WKBA25ED4305WKBA40ED4305WKBB25ED22305WKBB40ED22305WKBB25ED42305WKBB40ED42305WKBB25ED44305WKBB40ED44305W13KBA25ED2303WKBA40ED2303WKBA25ED4303WKBA40ED4303WKBB25ED22303WKBB40ED22303W----1.52KBA25ED2302W-KBA25ED4302W--------0KBA25ED2300WKBA40ED2300WKBA25ED4300WKBA40ED4300WKBB25ED22300WKBB40ED22300WKBB25ED42300WKBB40ED42300WKBB25ED44300WKBB40ED44300W20.53KBA40ED2203WKBA40ED2203WKBA40ED4203WKBA40ED4203WKBB40ED22203WKBB40ED22203WKBB40ED42203WKBB40ED42203WKBB40ED44203WKBB40ED44203W12--KBA25ED4202W-------AB - Feed unitsKBA25ABG4WMountingTerminals (mm²)Cable gland max Ø (mm)Catalogue numbersOrder in multiples of 1Catalogue numbersOrder in multiples of 1Left4PG16 Ø15KBA25ABG4W-KBA25ABG4W-------KBB40ABG44WKBA40ABG4WLeft10PG21 Ø19KBA40ABG4WKBA40ABG4WKBA40ABG4WKBA40ABG4WKBB40ABG44WKBB40ABG44WKBB40ABG44WKBB40ABG44WKBB40ABG44WKBB40ABG44WKBA40ABD4WRight10PG21 Ø19KBA40ABD4WKBA40ABD4WKBA40ABD4WKBA40ABD4W------KBB40ABT44WKBA40ABT4WCentral10PG21 Ø19KBA40ABT4WKBA40ABT4WKBA40ABT4WKBA40ABT4WKBB40ABT44WKBB40ABT44WKBB40ABT44WKBB40ABT44WKBB40ABT44WKBB40ABT44WDF - Flexibles KBB40DF420W- KBB40DF4420WKBB40DF405W - KBB40DF4405WKBA40DF420WKBA40DF405WType of componentLength (m)Catalogue numbersOrder in multiples of 1Catalogue numbersOrder in multiples of 1Flexible0.5KBA40DF405WKBA40DF405WKBA40DF405WKBA40DF405WKBB40DF405WKBB40DF405WKBB40DF4405WKBB40DF4405WKBB40DF4405WKBB40DF4405W2KBA40DF420WKBA40DF420WKBA40DF420WKBA40DF420WKBB40DF420WKBB40DF420WKBB40DF4420WKBB40DF4420WKBB40DF4420WKBB40DF4420WZF - Fixing bracketsKBA40ZFUKBB40ZFUType of componentMountingCatalogue numbersOrder in multiples of 10Catalogue numbersOrder in multiples of 10Universal fixing bracketSuspended on threaded rod or lateral (except wall)KBA40ZFUKBA40ZFUKBA40ZFUKBA40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBA40ZFSUKBB40ZFSUCable suspension systemWith 3 m steel cableKBA40ZFSUKBA40ZFSUKBA40ZFSUKBA40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUC
26www.se.comCatalogue numbersClassic offerLine components - Reinforced single circuitPEL1NL2L1L3NPE25 A40 A25 A40 AED - Straight lengthsKBB25ED●●●●WLength (m)Distance between outlets (m)Number of outletsCatalogue numbersOrder in multiples of 6313KBB25ED2303WKBB40ED2303WKBB25ED4303WKBB40ED4303W-0KBB25ED2300WKBB40ED2300WKBB25ED4300WKBB40ED4300W21.52KBB40ED2202WKBB40ED2202WKBB40ED4202WKBB40ED4202WAB - Feed unitsKBB40ABG4WMountingTerminals (mm²)Cable gland max Ø (mm)Catalogue numbersOrder in multiples of 1Left6 to 10PG21 Ø19KBB40ABG4WKBB40ABG4WKBB40ABG4WKBB40ABG4WKBB40ABD4WRight6 to 10PG21 Ø19KBB40ABD4WKBB40ABD4WKBB40ABD4WKBB40ABD4WKBB40ABT4WCentral6 to 10PG21 Ø19KBB40ABT4WKBB40ABT4WKBB40ABT4WKBB40ABT4WDF - Flexibles KBB40DF420WKBB40DF405WType of componentLength (m)Catalogue numbersOrder in multiples of 1Flexible0.5KBB40DF405WKBB40DF405WKBB40DF405WKBB40DF405W2KBB40DF420WKBB40DF420WKBB40DF420WKBB40DF420WZF - Fixing bracketsKBB40ZFUType of componentMountingCatalogue numbersOrder in multiples of 10Universal fixing bracketSuspended on threaded rod or lateral (except wall)KBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFSUCable suspension systemWth 3 m steel cableKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSU
27www.se.comC
28www.se.comCatalogue numbersClassic offerConnectorsL1NPE PEL1N PEL1NL1N L2L1L3NL1NPEL2L1L3NPE L2L1L3NPE L2L1L3NL2L1L3NPE L2L1L3NL1NPE Connector mounting side25 or 40 A25 or 40 ADCS - 10 A - Connectors direct pre-wired - 0.8 mKBC10DCS101KBC10DCS201KBC10DCS301PolaritySchemeColorCatalogue numbersOrder in multiples of 10L1 + NPEL1NGreenKBC10DCS101KBC10DCS101L2 + NPEL2NYellow-KBC10DCS201L3 + NPEL3NBrown-KBC10DCS301DCC - 10 A - Connectors direct pre-wired - 0.8 m - With phase selectionKBC10DCC211L1 + N or L2 + N or L3 + NPEL3L1L2N-KBC10DCC211KBC10DCC211DCB - 10 A - Connectors direct not wired - With phase selectionKBC10DCB●0L1 + N orL2 + N orL3 + NPEL3L1L2N-KBC10DCB20KBC10DCB203L + NPEL3L1L2N-KBC10DCB40KBC10DCB40DCB - 16 A - Connectors direct not wired - With phase selectionKBC16DCB●●L1 + N orL2 + N orL3 + NPEL3L1L2N-KBC16DCB23KBC16DCB233L + N PEL3L1L2N--KBC16DCB41L1 + L2 orL1 + L3 orL2 + L3PEL3L1L2-KBC16DCB24KBC16DCB24DCF - 16 A - Connectors for fuses not wired - With phase selectionKBC16DCF22KBC16DCF21KBC16DCF40PolaritySchemeProtectionCatalogue numbersOrder in multiples of 10L1 + N orL2 + N orL3 + N PEL3L1L2NCylindrical fuseNF 8.5 x 31.5 mmKBC16DCF21KBC16DCF213L + NPEL3L1L2NCylindrical fuseNF 8.5 x 31.5 mm-KBC16DCF40L1 + L2 orL1 + L3 orL2 + L3PEL3L1L2Cylindrical fuseNF 8.5 x 31.5 mmKBC16DCF22KBC16DCF22DCP - 16 A - Connectors with fuse and power socket not wired - With phase selectionKBC16DCP●PolaritySchemeProtectionCatalogue numbersOrder in multiples of 1L1 + N orL2 + N orL3 + NPEL3L1L2NNF 2P+T 10/16 A, 250 VKBC16DCP1KBC16DCP1L1 + N orL2 + N orL3 + NVDE 2P+T 10/16 A, 250 VKBC16DCP2KBC16DCP2
29www.se.com L2L1L3N(N2)(N3)PE25 or 40 ADCB - 16 A - Connectors direct not wired - With fixed polarityPolaritySchemeCatalogue numbersOrder in multiples of 10KBC16DCB216KBC16DCB226L2 + N2PEL3N2L2N3KBC16DCB226L3 + N3PEL3N2L2N3KBC16DCB216DCF - 16 A - Connectors for fuses not wired - With fixed polarityKBC16DCF216KBC16DCF226PolaritySchemeProtectionCatalogue numbersOrder in multiples of 10L2 + N2PEL3N2L2N3Cylindrical fuseNF 8.5 x 31.5 mmKBC16DCF226L3 + N3PEL3N2L2N3Cylindrical fuseNF 8.5 x 31.5 mmKBC16DCF216Catalogue numbersClassic offerConnectors for 2 mono circuitsC
30www.se.comCatalogue numbersControl systemLine components for DALI protocolDALI +DALI -LNPEL2L1L3NDALI +DALI -PE25 A40 A25 A40 AED - Straight lengthsKBA●●ED●●●●●WKBB●●ED●●●●●WLength (m)Distance between outlets (m)Number of outletsCatalogue numbersOrder in multiples of 630.55KBA25ED4305WKBA40ED4305WKBB25ED42305WKBB40ED42305W13KBA25ED4303WKBA40ED4303W--1.52KBA25ED4302W----0KBA25ED4300WKBA40ED4300WKBB25ED42300WKBB40ED42300W213KBA40ED4203WKBA40ED4203WKBB40ED42203WKBB40ED42203W1.52KBA25ED4202W---AB - Feed unitsKBA25ABG4WMountingTerminals (mm²)Cable gland max Ø (mm)Catalogue numbersOrder in multiples of 1Left4PG16 Ø15KBA25ABG4W---KBB40ABG44WKBA40ABG4WLeft10PG21 Ø19KBA40ABG4WKBA40ABG4WKBB40ABG44WKBB40ABG44WKBA40ABD4WRight10PG21 Ø19KBA40ABD4WKBA40ABD4W--KBB40ABT44WKBA40ABT4WCentral10PG21 Ø19KBA40ABT4WKBA40ABT4WKBB40ABT44WKBB40ABT44WDF - Flexibles KBB40DF4420WKBB40DF4405WKBA40DF420WKBA40DF405WType of componentLength (m)Catalogue numbersOrder in multiples of 1Flexible0.5KBA40DF405WKBA40DF405WKBB40DF4405WKBB40DF4405W2KBA40DF420WKBA40DF420WKBB40DF4420WKBB40DF4420WZF - Fixing bracketsKBA40ZFUKBB40ZFUType of componentMountingCatalogue numbersOrder in multiples of 10Universal fixing bracketSuspended on threaded rod or lateral (except wall)KBA40ZFUKBA40ZFUKBB40ZFUKBB40ZFUKBA40ZFSUKBB40ZFSUCable suspension systemwith 3 m steel cableKBA40ZFSUKBA40ZFSUKBB40ZFSUKBB40ZFSU
31www.se.comCatalogue numbersControl systemConnectors for DALI protocolL2L1L3NDALI +DALI -PE DALI +DALI -LNPE L2L1L3NDALI +DALI -PE Connector mounting side25 or 40 A25 or 40 ADCS - 10 A - Connectors direct pre-wired - 0.8 mKBC10DCS101KBC10DCS201KBC10DCS301PolaritySchemeColorCatalogue numbersOrder in multiples of 10L1 + NPEL1NGreenKBC10DCS101KBC10DCS101L2 + NPEL2NYellow-KBC10DCS201L3 + NPEL3NBrown-KBC10DCS301DCC - 10 A - Connectors direct pre-wired - 0.8 m - With phase selectionKBC10DCC211L1 + N orL2 + N orL3 + NPEL3L1L2N-KBC10DCC211KBC10DCC211DCB - 10 A - Connectors direct not wired - With phase selectionKBC10DCB●0L1 + N orL2 + N orL3 + NPEL3L1L2N-KBC10DCB20KBC10DCB203L + NPEL3L1L2N-KBC10DCB40KBC10DCB40DCB - 16 A - Connectors direct not wired - With phase selectionKBC16DCB●●L1 + N orL2 + N orL3 + NPEL3L1L2N-KBC16DCB23KBC16DCB233L + NPEL3L1L2N--KBC16DCB41L1 + L2 orL1 + L3 orL2 + L3PEL3L1L2-KBC16DCB24KBC16DCB24DCF - 16 A - Connectors for fuses not wired - With phase selectionKBC16DCF22KBC16DCF21KBC16DCF40PolaritySchemeProtectionCatalogue numbersOrder in multiples of 10L1 + N orL2 + N orL3 + NPEL3L1L2NCylindrical fuseNF 8.5 x 31.5 mmKBC16DCF21KBC16DCF213L + NPEL3L1L2NCylindrical fuseNF 8.5 x 31.5 mm-KBC16DCF40L1 + L2 orL1 + L3 orL2 + L3PEL3L1L2Cylindrical fuseNF 8.5 x 31.5 mmKBC16DCF22KBC16DCF22DCP - 16 A - Connectors with fuse and power socket not wired - With phase selectionKBC16DCP●PolaritySchemeProtectionCatalogue numbersOrder in multiples of 1L1 + N orL2 + N orL3 + NPEL3L1L2NNF 2P+T 10/16 A, 250 VKBC16DCP1KBC16DCP1L1 + N orL2 + N orL3 + NVDE 2P+T 10/16 A, 250 VKBC16DCP2KBC16DCP2C
32www.se.comKNXDALI +DALI - LNPEL2L1L3NDALI +DALI - PEKNX25 A40 A25 A40 AED - Straight lengthsKBA●●ED●●●●TWKBB●●ED●●●●●TWType of componentLength (m)Number of outletsCatalogue numbersOrder in multiples of 6Distribution length35KBA25ED4305TWKBA40ED4305TWKBB25ED42305TWKBB40ED42305TW3KBA25ED4303TWKBA40ED4303TW--23KBA40ED4203TWKBA40ED4203TWKBB40ED42203TWKBB40ED42203TWAB - Feed unitsKBB40ABG44TWKBA40ABG4TWMountingTerminals (mm²)Cable gland max Ø (mm)Catalogue numbersOrder in multiples of 1Left10PG21 Ø19KBA40ABG4TWKBA40ABG4TWKBB40ABG44TWKBB40ABG44TWKBB40ABD44TWKBA40ABD4TWRight10PG21 Ø19KBA40ABD4TWKBA40ABD4TWKBB40ABD44TWKBB40ABD44TWKBB40ABT44TWKBA40ABT4TWCentral10PG21 Ø19KBA40ABT4TWKBA40ABT4TWKBB40ABT44TWKBB40ABT44TWDF - Flexibles KBB40DF4420TWKBB40DF4405TWKBA40DF420TWKBA40DF405TWType of componentLength (m)Catalogue numbersOrder in multiples of 1Flexible0.5KBA40DF405TWKBA40DF405TWKBB40DF4405TWKBB40DF4405TW2KBA40DF420TWKBA40DF420TWKBB40DF4420TWKBB40DF4420TWZF - Fixing bracketsKBA40ZFUKBB40ZFUType of componentMountingCatalogue numbersOrder in multiples of 10Universal fixing bracketSuspended on threaded rod or lateral (except wall)KBA40ZFUKBA40ZFUKBB40ZFUKBB40ZFUKBA40ZFSUKBB40ZFSUCable suspension systemWith 3m steel cableKBA40ZFSUKBA40ZFSUKBB40ZFSUKBB40ZFSUCatalogue numbersControl systemLine components for combined DALI and KNX protocols
33www.se.comCatalogue numbersControl systemConnectors for combined DALI and KNX protocolsKNXDALI +DALI - LNPEL2L1L3NDALI +DALI - PEKNX Connector mounting side25 or 40 A25 or 40 ADCS - 16 A - Connectors direct pre-wired - 1 mKBC16DCS101TPolaritySchemeColorCatalogue numbersOrder in multiples of 10L1 + NDALI +/- KNX +/-PEL1NGreen-KBC16DCS101TKBC16DCS201TL2 + NDALI +/- KNX +/-PEL2NYellow-KBC16DCS201TKBC16DCS301TL3 + NDALI +/- KNX +/-PEL3NBrown-KBC16DCS301TDCB - 16 A - Connectors direct not wired - With phase selectionKBC16DCB22KBC16DCB21KBC16DCB40KBC16ZT1L1 + N or L2 + N orL3 + NDALI +/- KNX +/-PEL3L1L2N--KBC16DCB21+KBC16ZT13L + NDALI +/- KNX +/-PEL3L1L2N-KBC16DCB40+KBC16ZT1KBC16DCB40+KBC16ZT1L1 + L2 orL1 + L3 orL2 + L3DALI +/- KNX +/-PEL3L1L2--KBC16DCB22+KBC16ZT1DCF - 16 A - Connectors for fuses not wired - With phase selectionKBC16DCF22KBC16DCF21KBC16DCF40KBC16ZT1PolaritySchemeProtectionCatalogue numbersOrder in multiples of 10L1 + N orL2 + N orL3 + NDALI +/-KNX +/-PEL3L1L2NCylindrical fuseNF 8.5 x 31.5 mm-KBC16DCF21+KBC16ZT13L + NDALI +/-KNX +/-PEL3L1L2NCylindrical fuseNF 8.5 x 31.5 mmKBC16DCF40+KBC16ZT1KBC16DCF40+KBC16ZT1L1 + L2 orL1 + L3 orL2 + L3DALI +/-KNX +/-PEL3L1L2Cylindrical fuseNF 8.5 x 31.5 mm-KBC16DCF22+KBC16ZT1DCP - 16 A - Connectors for fuses with power sockets not wired - With phase selectionKBC16DCP●KBC16ZT1PolaritySchemeProtectionCatalogue numbersOrder in multiples of 1L1 + N orL2 + N orL3 + NDALI +/-KNX +/-PEL3L1L2NNF 2P+T 10/16 A, 250 V-KBC16DCP1+KBC16ZT1L1 + N orL2 + N orL3 + NDALI +/-KNX +/-VDE 2P+T 10/16 A, 250 V-KBC16DCP2+KBC16ZT1C
34www.se.comCatalogue numbersControl systemLine components for KNX alone or others protocolsL1NPEBUSBUSL2L1L3NPEPEL1NL1NBUSL2L1L3NL1NPEBUSL2L1L3NL2L1L3NPEBUSL2L1L3NL2L1L3NPEBUS25 A40 A25 A40 A25 A40 A25 A40 A25 A40 A40 AED - Straight lengthsKBA●●ED●●●●TWKBB●●ED●●●●●●●WLength (m)Distance between outlets (m)Number of outletsCatalogue numbersOrder in multiples of 6Catalogue numbersOrder in multiples of 630.55KBA25ED2305TWKBA40ED2305TWKBA25ED4305TWKBA40ED4305TWKBB25ED22305TWKBB40ED22305TWKBB25ED42305TWKBB40ED42305TWKBB25ED44305TWKBB40ED44305TWKBB40ED44305T2W13KBA25ED2303TWKBA40ED2303TWKBA25ED4303TWKBA40ED4303TW-------213KBA40ED2203TWKBA40ED2203TWKBA40ED4203TWKBA40ED4203TWKBB40ED22203TWKBB40ED22203TWKBB40ED42203TWKBB40ED42203TWKBB40ED44203TWKBB40ED44203TW-AB - Feed unitsKBB40ABG44TWKBA40ABG4TWMountingTerminals (mm²)Cable gland max Ø (mm)Catalogue numbersOrder in multiples of 1Catalogue numbersOrder in multiples of 1Left10PG21 Ø19KBA40ABG4TWKBA40ABG4TWKBA40ABG4TWKBA40ABG4TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44T2WKBB40ABD44TWKBA40ABD4TWRight10PG21 Ø19KBA40ABD4TWKBA40ABD4TWKBA40ABD4TWKBA40ABD4TWKBB40ABD44TWKBB40ABD44TWKBB40ABD44TWKBB40ABD44TWKBB40ABD44TWKBB40ABD44TW-KBB40ABT44TWKBA40ABT4TWCentral10PG21 Ø19KBA40ABT4TWKBA40ABT4TWKBA40ABT4TWKBA40ABT4TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWDF - Flexibles KBB40DF4420TWKBB40DF4405TWKBA40DF420TWKBA40DF405TWType of componentLength (m)Catalogue numbersOrder in multiples of 1Catalogue numbersOrder in multiples of 1Flexible0.5KBA40DF405TWKBA40DF405TWKBA40DF405TWKBA40DF405TWKBB40DF4405TWKBB40DF4405TWKBB40DF4405TWKBB40DF4405TWKBB40DF4405TWKBB40DF4405TW-2KBA40DF420TWKBA40DF420TWKBA40DF420TWKBA40DF420TWKBB40DF4420TWKBB40DF4420TWKBB40DF4420TWKBB40DF4420TWKBB40DF4420TWKBB40DF4420TW-ZF - Fixing bracketsKBA40ZFUKBB40ZFUType of componentMountingCatalogue numbersOrder in multiples of 10Catalogue numbersOrder in multiples of 10Universal fixing bracketSuspended on threaded rod or lateral (except wall)KBA40ZFUKBA40ZFUKBA40ZFUKBA40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBA40ZFSUKBB40ZFSUCable suspension systemWith 3m steel cableKBA40ZFSUKBA40ZFSUKBA40ZFSUKBA40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSU
35www.se.comL1NPEBUSBUSL2L1L3NPEPEL1NL1NBUSL2L1L3NL1NPEBUSL2L1L3NL2L1L3NPEBUSL2L1L3NL2L1L3NPEBUS25 A40 A25 A40 A25 A40 A25 A40 A25 A40 A40 AED - Straight lengthsKBA●●ED●●●●TWKBB●●ED●●●●●●●WLength (m)Distance between outlets (m)Number of outletsCatalogue numbersOrder in multiples of 6Catalogue numbersOrder in multiples of 630.55KBA25ED2305TWKBA40ED2305TWKBA25ED4305TWKBA40ED4305TWKBB25ED22305TWKBB40ED22305TWKBB25ED42305TWKBB40ED42305TWKBB25ED44305TWKBB40ED44305TWKBB40ED44305T2W13KBA25ED2303TWKBA40ED2303TWKBA25ED4303TWKBA40ED4303TW-------213KBA40ED2203TWKBA40ED2203TWKBA40ED4203TWKBA40ED4203TWKBB40ED22203TWKBB40ED22203TWKBB40ED42203TWKBB40ED42203TWKBB40ED44203TWKBB40ED44203TW-AB - Feed unitsKBB40ABG44TWKBA40ABG4TWMountingTerminals (mm²)Cable gland max Ø (mm)Catalogue numbersOrder in multiples of 1Catalogue numbersOrder in multiples of 1Left10PG21 Ø19KBA40ABG4TWKBA40ABG4TWKBA40ABG4TWKBA40ABG4TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44TWKBB40ABG44T2WKBB40ABD44TWKBA40ABD4TWRight10PG21 Ø19KBA40ABD4TWKBA40ABD4TWKBA40ABD4TWKBA40ABD4TWKBB40ABD44TWKBB40ABD44TWKBB40ABD44TWKBB40ABD44TWKBB40ABD44TWKBB40ABD44TW-KBB40ABT44TWKBA40ABT4TWCentral10PG21 Ø19KBA40ABT4TWKBA40ABT4TWKBA40ABT4TWKBA40ABT4TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWKBB40ABT44TWDF - Flexibles KBB40DF4420TWKBB40DF4405TWKBA40DF420TWKBA40DF405TWType of componentLength (m)Catalogue numbersOrder in multiples of 1Catalogue numbersOrder in multiples of 1Flexible0.5KBA40DF405TWKBA40DF405TWKBA40DF405TWKBA40DF405TWKBB40DF4405TWKBB40DF4405TWKBB40DF4405TWKBB40DF4405TWKBB40DF4405TWKBB40DF4405TW-2KBA40DF420TWKBA40DF420TWKBA40DF420TWKBA40DF420TWKBB40DF4420TWKBB40DF4420TWKBB40DF4420TWKBB40DF4420TWKBB40DF4420TWKBB40DF4420TW-ZF - Fixing bracketsKBA40ZFUKBB40ZFUType of componentMountingCatalogue numbersOrder in multiples of 10Catalogue numbersOrder in multiples of 10Universal fixing bracketSuspended on threaded rod or lateral (except wall)KBA40ZFUKBA40ZFUKBA40ZFUKBA40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBB40ZFUKBA40ZFSUKBB40ZFSUCable suspension systemWith 3m steel cableKBA40ZFSUKBA40ZFSUKBA40ZFSUKBA40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUKBB40ZFSUC
36www.se.comCatalogue numbersControl systemConnectors for KNX alone or others protocolsL1NPEBUS PEL1NL1NBUSBUSL2L1L3NPE L2L1L3NL1NPEBUS L2L1L3NL2L1L3NPEBUS Connector mounting side25 or 40 A25 or 40 ADCS - 16 A - Connectors direct pre-wired - 1 mKBC16DCS101TPolaritySchemeColorCatalogue numbersOrder in multiples of 10L1 + N BUS +/-PEL1NGreenKBC16DCS101TKBC16DCS101TKBC16DCS201TL2 + NBUS +/-PEL2NYellow-KBC16DCS201TKBC16DCS301TL3 + NBUS +/-PEL3NBrown-KBC16DCS301TDCB - 16 A - Connectors direct not wiredKBC16DCB22KBC16DCB21KBC16DCB40KBC16ZT1L1 + N or L2 + N orL3 + NBUS +/-PEL3L1L2N-KBC16DCB21+KBC16ZT1KBC16DCB21+KBC16ZT13L + NBUS +/-PEL3L1L2N--KBC16DCB40+KBC16ZT1L1 + L2 orL1 + L3 orL2 + L3BUS +/-PEL3L1L2--KBC16DCB22+KBC16ZT1DCF - 16 A - Connectors for fuses not wiredKBC16DCF22KBC16DCF21KBC16DCF40KBC16ZT1PolaritySchemeProtectionCatalogue numbersOrder in multiples of 10L1 + N orL2 + N orL3 + NBUS +/-PEL3L1L2NCylindrical fuseNF 8.5 x 31.5 mmKBC16DCF21+KBC16ZT1KBC16DCF21+KBC16ZT13L + NBUS +/-PEL3L1L2NCylindrical fuseNF 8.5 x 31.5 mm-KBC16DCF40+KBC16ZT1L1 + L2 orL1 + L3 orL2 + L3BUS +/-PEL3L1L2Cylindrical fuseNF 8.5 x 31.5 mm-KBC16DCF22+KBC16ZT1DCP - 16 A - Connectors for fuses with power sockets not wiredKBC16DCP●KBC16ZT1PolaritySchemeProtectionCatalogue numbersOrder in multiples of 1L1 + N orL2 + N orL3 + NBUS +/-PEL3L1L2NNF 2P+T 10/16 A, 250 VKBC16DCP1+KBC16ZT1KBC16DCP1+KBC16ZT1L1 + N orL2 + N orL3 + NBUS +/-VDE 2P+T 10/16 A, 250 VKBC16DCP2+KBC16ZT1KBC16DCP2+KBC16ZT1
37www.se.comC
38www.se.comCatalogue numbersAll versionsFixing bracketsKBAKBBZF - Fixing bracketsKBA40ZFUKBB40ZFUType of componentMountingOrder in multiples ofCatalogue numbersUniversal fixing bracketSuspended on threaded rod or lateral (except wall)10KBA40ZFUKBB40ZFUKB●40ZFS23KB●40ZFSUKB●40ZFSLCable suspension systemWith steel cable10KBA40ZFSUKBB40ZFSUFor steel cable10KBA40ZFSLKBB40ZFSL3 m steel cable alone10KBB40ZFS23KBB40ZFS23KBA40ZFU2W KBB40ZFU2WDouble universal fixing bracketFor pigtail or open hook to suspend the luminaire1KBA40ZFU2WKBB40ZFU2WKBB40ZFPUKBB40ZFMPKBB40ZFC5KBB40ZFC6KBB40ZFCKBB40ZFLSpring fixing bracketAdjustable for threaded rod, M610KBA40ZFPUKBB40ZFPUPigtail hookSuspended by small chain10KBB40ZFCKBB40ZFCRaiserFor mounting on wall or false floor10KBB40ZFMPKBB40ZFMPOpen hookTo suspend the luminaire10KBB40ZFC5KBB40ZFC5RingMounted on the luminaire10KBB40ZFC6KBB40ZFC6Fixing bracketFor direct suspension of luminaireson KBB12-KBB40ZFLCable duct supportKFB25CD253Type of componentMountingOrder in multiples ofCatalogue numbersCable ductWidth 25 mm, length 3 m6KFB25CD253KFB25CD253KBB40ZFG1Cable duct supportTo bemounted on a spring fixingbracket (1)10KBB40ZFG1KBB40ZFG1KB●40ZFG2Cable duct support + intermediate support (2)10KBA40ZFG2KBB40ZFG2KBB40ZFGUCable bracketFor adjacent circuits20KBB40ZFGUKBB40ZFGU(1) Maximun recommended distance between fixings: 2 meters.(2) Maximun recommended distance between fixings: 3 meters.
39www.se.comCatalogue numbersAll versionsAccessoriesKBAKBBOther accessoriesKBC16ZL10KBC16ZL20KBC16ZL30Type of componentMountingColorOrder in multiples ofCatalogue numbersOutlet/connector unit interlocking device (2 parts)Identification and mechanical interlocking between 1 to 3 different circuitsBlue20KBC16ZL10KBC16ZL10White20KBC16ZL20KBC16ZL20Red20KBC16ZL30KBC16ZL30KBC16ZT1Bus connection deviceFor 16 A single-phase or three-phase connector to connect the remote control circuit of the trunking to the remote receiver10KBC16ZT1KBC16ZT1KBC16ZB1Blanking plateRestore IP55 on connectoroutlet if original blankingplate is lost10KBC16ZB1KBC16ZB1KBC16ZC1Rear support bracketFor securing 16 A single-phase connector to the trunking10KBC16ZC1KBC16ZC1KBA40AFKBB40AFEnd coverSpare part5KBA40AF-10KBB40AFKB●40EDA20WEmpty lengthUsed to adjust line length to building dimensions.Two metres long, can be cut on site.1KBA40EDA20WKBB40EDA20WAdditional jointing unit1 circuit1-KBB40ZJ4W2 circuits1-KBB40ZJ44W2 circuits + bus1-KBB40ZJ44TWC
40www.se.comDimensionsComponents and fixationsCanalis KBAED - Straight lengthsKBAppEDp300WKBAppEDp302WKBAppEDp303W, KBAppEDp303TWKBAppEDp305W, KBAppEDp305TWKBAppEDp203W, KBAppEDp203TWKBAppEDp202WKBA40EDA20WAB - Feed unitsKBA25ABG4WKBA40ABG4W, KBA40ABG4TW177562206KBA40ABD4W, KBA40ABD4TWKBA40ABT4W, KBA40ABT4TWDF - FlexiblesKBA40DF405W, KBA40DF405TWKBA40DF420W, KBA40DF420TWZF - Fixing bracketsKBA40ZFUKBA40ZFSUKBA40ZFPUKBB40ZFCKBB40ZFMPKBB40ZFC5KBB40ZFC6The end cover KBA is a spare part of the after-sales service ref KBA40AF
41www.se.comDimensionsComponents and fixationsCanalis KBBAB - Feed units177427128,5 The end cover KBB is a spare part of the after-sales service ref KBB40AFKBB40ABG4W, KBB40ABG4TWKBB40ABD4W, KBB40ABD4TWKBB40ABT44W, KBB40ABT44TWEnd coverKBB40ABp44W, /KBB40ABp4TW, KBB40ABG44T2WDF - FlexiblesLength (mm)abKBB40DFpp05W, KBB40DFpp05TW153500KBB40DFpp20W, KBB40DFpp20TW16532000KBB40DF405W, KBB40DF420W, KBB40DF4405W, KBB40DF4420W, KBB40DF405TW, KBB40DF420TW, KBB40DF4405TW, KBB40DF4420TWZF - Fixing bracketsKBB40ZFUKBB40ZFSUKBB40ZFPUKBB40ZFCKBB40ZFMP46407435Ø6.27046577435Ø6.270KBB40ZFLKBB40ZFUKBB40ZFC5KBA40ZFU2WKBB40ZFU2WKBB40ZFC6ED - Straight lengthsKBBppEDp300WKBB40EDA20WKBBppEDp303W, KBBppEDp303TWKBBppEDpp202W, KBBppEDpp202TWFL2L1L3NL1NPEView F====KBBppEDpp305W, KBBppEDpp305TWD
42www.se.comDimensionsComponents and fixationsCanalis KBCAccessories3146Ø: 13 mm (x 3)Max: Ø 16 mmKFB25CD253KBB40ZFG1KBA40ZFG2KBB40ZFG2KBB40ZFGUDC - ConnectorsKBC10DCS101, KBC10DCS201, KBC10DCS301KBC10DCS101T, KBC10DCS201T, KBC10DCS301TKBC10DCC211, KBC10DCB20, KBC10DCB40KBC16DCB21, KBC16DCB22, KBC16DCB216 , KBC16DCB226, KBC16DCF21, KBC16DCF22, KBC16DCF216, KBC16DCF226 KBC16DCB40, KBC16DCF40,KBC16DCP1, KBC16DCP2
43www.se.comD
44www.se.comRun component characteristicsRating of trunking (A)2540General characteristicsCompliance with standardsIEC/EN 61439-6IEC/EN 61439-6Degree of protectionIP5555Mechanical impactsIK0606ColorRAL 9003 whiteRAL 9003 whitePolarityL1NPE or L2L1L3NPEL1NPE or L2L1L3NPENumber of live conductors2 or 42 or 4Rated current at an ambient temperature of 35°CIncA2540Rated insulation voltageUiV690690Rated operational voltageUeV230...400230...400Rated impulse voltageUimpkV44Rated frequencyfHz50/6050/60Conductor characteristicsPhase conductorsMean resistance at an ambient temperature of 20°CR20mΩ/m6.802.83Mean resistance at Inc and 35°CR1mΩ/m8.303.46Mean reactance at Inc, 35°C and 50 HzX1mΩ/m0.020.02Mean impedance at Inc, 35°C and 50 HzZ1mΩ/m8.333.46Protective conductor (PE)Mean resistance at an ambient temperature of 20°CmΩ/m1.571.57Fault loop characteristicsSymmetrical components methodPh/Nat 20°CMean resistanceR0 ph/NmΩ/m27.2119.40Mean reactanceX0 ph/NmΩ/m0.850.38Mean impedanceZ0 ph/NmΩ/m27.2219.41Ph/PEat 20°CMean resistanceR0 ph/PEmΩ/m19.4013.83Mean reactanceX0 ph/PEmΩ/m0.380.73Mean impedanceZ0 ph/PEmΩ/m19.4113.85Impedance methodAt 20°CMean resistancePh/PhRb0 ph/phmΩ/m13.615.68Ph/NRb0 ph/NmΩ/m13.615.68Ph/PERb0 ph/PEmΩ/m11.017.66For Incat 35°CMean resistancePh/PhRb1 ph/phmΩ/m16.606.91Ph/NRb1 ph/NmΩ/m16.606.91Ph/PERb1 ph/PEmΩ/m12.508.70For Incat 35°C and50 HzMean reactancePh/PhXb ph/phmΩ/m0.040.90Ph/NXb ph/NmΩ/m0.040.90Ph/PEXb ph/PEmΩ/m0.0350.035Other characteristicsShort-circuit withstand capacityRated peak withstand currentIpkkA4.409.60Maximum thermal limit I2tA2s195 x 103900 x 103Rated short-time withstand current (t = 1 s)IcwkA0.440.94Voltage dropComposite voltage drop (hot state) expressed in V/100 m/A (50 Hz) with the load uniformly distributed over the run. If the load is concentrated at one end of the run, the voltage drop is twice the value indicated in the table.For a power factor of1V/100 m/A0.720.300.9V/100 m/A0.670.280.8V/100 m/A0.610.250.7V/100 m/A0.540.22This table is given for three-phases network. The single phase voltage drop is obtained bydividing the three-phase voltage drop indicated above by 0.866. For lower neutral / neutral voltage phase, we divide the voltage drop above by 1.732.Radiated magnetic fieldRadiated magnetic field strength 1 metre from the trunkingBμT< 2 x 10-3< 2 x 10-3Derating in case of harmonicsOperational current as a function of 3rd harmonic contentTHD y 15 %254015 % < THD y 33 %2032THD > 33 %1628Permissible current as a function of ambient temperatureAmbient temperature°C< 353540455055Cœfficient K1%n/a10.960.930.890.85Design guideCharacteristicsCanalis KBA
45www.se.comDesign guideCharacteristicsCanalis KBBRun component characteristicsRating of trunking (A)2540General characteristicsCompliance with standardsIEC/EN 61439-6IEC/EN 61439-6Degree of protectionIP5555Mechanical impactsIK0606ColorRAL 9003 whiteRAL 9003 whitePolarityIf polarityL+NL1NPE3L+N and L+NL2L1L3NL1NPE3L+N and 3L+NL2L1L3NL2L1L3NPEL+NL1NPE3L+N and L+NL2L1L3NL1NPE3L+N and 3L+NL2L1L3NL2L1L3NPEoror3L+NL2L1L3NPE3L+NL2L1L3NPEL1 N L2 NConsult usNumber of circuits122122Rated current at an ambient temperature of 35°CIncA252323403838Rated insulation voltageUiV690690Rated operational voltageUeV230...400230...400Rated impulse voltageUimpkV44Rated frequencyfHz50/6050/60Conductor characteristicsPhase conductorsMean resistance at an ambient temperature of 20°CR20mΩ/m6.802.83Mean resistance at Inc and 35°CR1mΩ/m8.303.46Mean reactance at Inc, 35°C and 50 HzX1mΩ/m0.020.02Mean impedance at Inc, 35°C and 50 HzZ1mΩ/m8.333.46Protective conductor (PE)Mean resistance at an ambient temperature of 20°CmΩ/m0.800.80Other characteristicsShort-circuit withstand capacityRated peak withstand currentIpkkA4.409.60Maximum thermal limit I2tA2s195 x 103900 x 103Rated short-time withstand current (t = 1 s)IcwkA0.440.94Voltage dropComposite voltage drop (hot state) expressed in V/100 m/A (50 Hz) with the load uniformly distributed over the run. If the load is concentrated at one end of the run, the voltage drop is twice the value indicated in the table.For a power factor of1V/100 m/A0.720.300.9V/100 m/A0.670.280.8V/100 m/A0.610.250.7V/100 m/A0.550.22This table is given for three-phases network. The single phase voltage drop is obtained bydividing the three-phase voltage drop indicated above by 0.866. For lower neutral / neutral voltage phase, we divide the voltage drop above by 1.732.Radiated magnetic fieldRadiated magnetic field strength 1 metre from the trunkingBμT< 2 x 10-3< 2 x 10-3Derating in case of harmonicsOperational current as a function of 3rd harmonic contentTHD y 15 %254015 % < THD y 33 %2032THD > 33 %1628Permissible current as a function of ambient temperatureAmbient temperature°C< 353540455055Cœfficient K1%n/a10.960.930.890.85Fault loop characteristicsSymmetrical components methodPh/Nat 20°CMean resistanceR0 ph/NmΩ/m27.2117.28Mean reactanceX0 ph/NmΩ/m0.855.25Mean impedanceZ0 ph/NmΩ/m27.2218.06Ph/PEat 20°CMean resistanceR0 ph/PEmΩ/m17.2813.83Mean reactanceX0 ph/PEmΩ/m5.250.73Mean impedanceZ0 ph/PEmΩ/m18.0613.85Impedance methodAt 20°CMean resistancePh/PhRb0 ph/phmΩ/m13.615.68Ph/NRb0 ph/NmΩ/m13.615.68Ph/PERb0 ph/PEmΩ/m10.266.92For Incat 35°CMean resistancePh/PhRb1 ph/phmΩ/m16.596.92Ph/NRb1 ph/NmΩ/m16.596.92Ph/PERb1 ph/PEmΩ/m11.777.14For Incat 35°C and50 HzMean reactancePh/PhXb ph/phmΩ/m0.350.90Ph/NXb ph/NmΩ/m0.350.90Ph/PEXb ph/PEmΩ/m0.071.85E
46www.se.comConnector characteristicsType of connectorKBC10KBC10KBC16CBKBC16CFLighting controlGeneral characteristicsCompliance with standardsIEC/EN 61439-6Degree of protectionIP55555555Rated current at an ambient temperature of 35°CIncA10101616Rated insulation voltageUiV690400690400Rated operational voltageUeV230...400230...400230...400230...400Bus characteristicsDALIKNXCross-section and type of conductormm22 x 2.5 copper2 x 0.5 copperRated insulation voltage (Ui) (between power circuit and bus)V690500Rated operational voltage (Ue) (max. U between bus + and - poles) V230 to 40032Maximum operational current (Ie)A253.8Linear resistance mΩ/m5275Linear capacitance pF/m30100Maximum recommended lengthm300300Design guideCharacteristicsVoltage drop in the Canalis busbar trunkingThe table below indicates the three-phase voltage drop, in volts, in the Canalis busbar trunking (electrical power uniformly distributed).The single-phase voltage drop is obtained by dividing the three-phase voltage drop indicated below by 0.866.If the exact operational current (Ib) and length are not available, select the next highest.Type of CanalisOperationalLength of line (m)current (A)681012152025303540455060708010025 A KBA100.40.50.60.70.91.21.51.82.12.42.83.13.74.34.96.125 A KBB160.60.811.21.522.42.93.43.94.44.95.96.87.89.8cos 0.8200.711.31.51.82.43.13.74.34.95.56.17.38.69.812.2250.91.21.51.82.33.13.84.65.36.16.97.69.210.712.215.325 A KBA100.40.50.70.811.31.722.32.733.444.75.46.725 A KBB160.60.91.11.31.62.12.73.23.84.34.85.46.47.58.610.7cos 0.9200.81.11.31.622.73.444.75.466.789.410.713.42511.31.722.53.44.255.96.77.58.410.111.713.416.825 A KBA100.40.60.70.91.11.41.82.22.52.93.23.64.355.87.225 A KBB160.70.91.21.41.72.32.93.544.65.25.86.98.19.211.5cos 1200.91.21.41.72.22.93.64.355.86.57.28.610.111.514.4251.11.41.82.22.73.65.45.46.37.28.1941.812.614.41840 A KBA160.20.30.40.50.60.811.21.41.61.822.42.83.2440 A KBB200.30.40.50.60.711.21.51.722.22.533.545cos 0.8 250.40.50.60.70.91.21.61.92.22.52.83.13.74.456.2320.50.60.811.21.622.42.83.23.644.85.66.48400.60.811.21.522.533.544.556781040 A KBA160.30.40.40.50.70.91.11.31.61.822.22.73.13.64.540 A KBB200.30.40.60.70.81.11.41.722.22.52.83.43.94.55.6cos 0.9 250.40.60.70.81.11.41.82.12.52.83.23.54.24.95.67320.50.70.91.11.31.82.22.73.13.644.55.46.37.29400.70.91.11.31.72.22.83.43.94.555.66.77.8911.240 A KBA160.30.40.50.60.711.21.41.71.92.22.42.93.43.84.840 A KBB200.40.50.60.70.91.21.51.82.12.42.733.64.24.86cos 1 250.50.60.80.91.11.51.92.32.633.43.84.55.367.5320.60.811.21.41.92.42.93.43.84.33.85.86.77.79.6400.711.21.41.82.433.64.24.85.467.28.49.612Voltage-drop conversionOperational voltage (V)Voltage drop in volts for a given %0.30.511.522.533.544.556789102300.71.22.33.54.65.86.98.19.2101214161821234001.224681012141618202428323640
47www.se.com1. Identify the external influencesThe ambient temperature, presence of dust, condensation of water, etc. contribute to the definition of the degree of protection required in the area where the lines will be installed.Canalis KB has a degree of protection IP55 and is sprinkler resistant. It has a mechanical resistance IK06. As per the requirement of the IEC 61439-6 the operating ratings are given for an ambient temperature of 35°C.2. Identify the determinant dataL = Length of the line (m)D = Distance between each lightings (m)P = Power of lightings (W)F = Power factor of lightings (Cos φ)W = Weight of lighting (kg)N = Number of lightings per lineV = Voltage (Volt)3. Determine the maximun current carrier by the busbartrunking in operationN = Number of lightings per line = (L/D) - 1Max current = N x P / F / VExample:L = 95 mD = 3 mP = 80 WF = 0.8V = 230 Volt (L+N)N = (95/3) -1 = 31 - 1 = 30Max current = 30 x 80 / 0.8 / 230 = 13.04 AThe just above available rating is 25 A.4. Check if the voltage drop is below 3 %Use data pages 44 and 45 to determine the charactaristics of Canalis KBA 25 A and Canalis KBB 25 A.Canalis KBA 25 A:Voltage drop per 100 m / A for a power factor 0.8 = 0.61Voltage for 95 m: 0.61 x 13.04 x 0.95 = 7.55 VVoltage drop in %: 7.55 / 230 = 3.2 %The voltage drop is too high, the line length need to be reduced or a superior rating need to be selected.Examples of calculation are available page 46.5. Select the adapted overload and short-circuit protectionSee page 48 to page 51.6. Selected the most adapted product to support the lighting weightSee page 52.Design guideProcedure to select Canalis KB Ph + N distribution 3Ph + N balanced distributionE
48www.se.comPrecalculating XLPE or PVC cables + CanalisDrawn from the Ecodial low-voltage installation-calculation software, the information provided here assists in defining busbar trunking (cables and Canalis) and their protection in compliance with installation standards and calculation guide.Protection of the main busbar trunking (cable + Canalis) bThe tables below may be used to determine: vthe rated current (In) or the setting current (Ir) of the overload-protection devices, vthe rated current (Inc) of Canalis, vthe thermal minimum cross-section of cables. bThese three characteristics are defined for the following installation conditions: vmaximum ambient temperature 30°C, vcables placed in cable trays. Layout as a single horizontal layer or in groups of 2 or 3 cores.Connector protectionCanalis connectors must have overload protection. The connector is created using a fused connector unit to protect the cable (C3) and the device against short-circuits.This protection offers good discrimination during operation (continuity of service, trouble-shooting, etc.).For lighting, it may be useful to take advantage of the possibilities for dispensing with or remotely locating the protection, offered by standard IEC 60364-4-43 (§ 433 and 434) and summarised in the texts below, drawn from UTE C 15-107.The connector is created using a pre-wired connector unit.Supply to devices not subject to overloadsExemption possibilities: bthe C3 cable (connection to the device) does not need to be protected against overloads (NF C 15-100, 473.1.2b) or short-circuits (NF C 15-100, 473.2.2.1) because the cable: vis not subject to overload currents, vdoes not have connectors or power sockets, vis less than or equal to three metres, vis designed to reduce to a minimum the risk of short-circuits, vis not located near any flammable material. Example: luminaires, convectors, etc.Supply to devices with built-in overload protectionExemption possibilities: bthe device P2 protecting C3 cable against overloads is not positioned at the head (NF C 15-100, 473.1.1.2 b) of C3 because the latter: vdoes not have connectors or power sockets, vis less than or equal to three metres, vis designed to reduce to a minimum the risk of short-circuits, vis not located near any flammable material. NB: P1 - P2 are short-circuit protection devices.Design guideSelect the overload protection
49www.se.comDesign guideSelect the overload protectionPrecalculating XLPE or PVC cables + CanalisThe tables below determine, as a function of the type of overload protection (circuit breaker or fuse): bthe type of busbar trunking required bthe size of supply cables (in mm2) as a function of the installation method, for all conductor configurations.Protection by iC60 (curve C) modular circuit breakerType of busbar trunkingOperat. currentXLPE cablePVC cableSpacedTouching(number of cables)SpacedTouching(number of cables)Circuit-breaker rating (A)2 to 56 or more2 34 or more25 A KBA25 A KBB101.51.51.51.51.51.51.5161.51.51.51.52.52.52.5201.52.52.52.52.54425 A KBA25 A KBB252.5442.54462.5(1)2.5(1)40 A KBA40 A KBB32466466102.5(1)4(1)4(1)40461061010106(1) Protection by gG fusesType of busbar trunkingRated current(A)XLPE cablePVC cableSpacedTouching(number of cables)SpacedTouching(number of cables)2 to 56 or more2 34 or more25 A KBA25 A KBB101.51.51.51.51.51.51.5161.52.52.52.52.52.541.5 (1)202.52.52.52.54461.5 (1)25 A KBA25 A KBB252.54646664 (1)40 A KBA40 A KBB324666610102.5 (1)4 (1)(1) Permissible cable cross-sections for single-phase distribution. Cables spaced in cable trays. Cables touching in cable trays.E
50www.se.comDesign guideSelect the short-circuit protectionDetermining the prospective short-circuit current at the origin of the CanalisThere are two possible situations: bthe busbar trunking for lighting is supplied by a secondary switchboard. Isc(a): rms short-circuit current across the transformer terminals.Rms Isc (a) values across the transformer terminals (U = 400 V)Power (kVA)50100150200250315400500630800100012501600Isc(a) (kA)1.83.65.77.28.911.214.217.622.124.827.831.536.7Isc(b): downstream short-circuit current, less than Isc(a), limited by cable impedance.Isc(c): short-circuit current across circuit-breaker terminals, less than Isc(b), limited by circuit breaker.Isc(d): prospective short-circuit current, limited by cable impedance (case 1) or by impedance of cable + Canalis (case 2).Isc(e): prospective short-circuit current, at head of Canalis by the circuit breaker (d) and the impedance of the Canalis supply cable.Drawn from the Ecodial low-voltage installation-calculation software, produced by Schneider Electric for fast and precise evaluation of prospective short-circuit currents at different points in the circuit.Please consult your regional sales office.Canalis and protection coordinationDrawn from tests specified in standards (used in our guides and software), the table below determines the type of circuit breaker or fuse required for a particular type of busbar trunking depending on the prospective short-circuit current at the head of the Canalis trunking.Type of busbar trunkingCircuit-breaker protectionFuse protectionIsc (d) (Prospective Isc)Prospective Isc10 kA15 kA20 kA25 kA50 kA50 kA25 A KBA, 25 A KBBiC60N25iC60H25iC60L25iC60L25NC100LH2520 A gG40 A KBA, 40 A KBBiC60N40iC60H40iC60L40iC60L40NC100LH4032 A gGCharacteristics of Canalis busbar trunkingType of busbar trunkingShort-circuit withstandPermissible thermal stress for 0.1 s y t y 3 sRated peak short-circuit current(kA)(A2S)25 A KBA4.419.5 x 10440 A KBA9.690 x 10425 A KBB4.419.5 x 10440 A KBB9.690 x 104CableCableCanalis KBA or KBBCanalis KN or KSCanalis
51www.se.comDesign guideSelect the short-circuit protectionThe selection guides below can be used to determine the circuit breaker required to fully protect the trunking depending on the prospective short-circuit current of the installation.Example: in an installation with a prospective Isc of 15 kA, the circuit breaker required to protect 25 A KBB trunking is a iC60H (the rating depends on the rated current of the circuit).In bold, the most appropriate device to the rating of the busbar trunkingSelection guide for 230 / 240 VIsc max (kA rms) KBA2510 kA15 kA20 kA25 kACircuit breakeriC60N10/.../25iC60H10/.../25iC60L10/.../25iC60L10/.../25iC60N10/.../25iC60H10/.../25iC60L10/.../25iC60L10/.../25NG125N10/.../25Isc max (kA rms) KBB2510 kA15 kA20 kA25 kACircuit breakeriC60N10/.../25iC60H10/.../25iC60L10/.../25iC60L10/.../25iC60N10/.../25iC60H10/.../25iC60L10/.../25iC60L10/.../25NG125N10/.../25Isc max (kA rms) KBA4010 kA15 kA20 kA25 kA50 kACircuit breakeriC60N10/.../40iC60H10/.../40iC60L40iC60L10/.../25iC60N10/.../40iC60H10/.../40iC60L40iC60L10/.../25NG125N10/.../40NG125L10/.../40Isc max (kA rms) KBB4010 kA15 kA20 kA25 kA50 kACircuit breakeriC60N10/.../40iC60H10/.../40iC60L40iC60L10/.../25iC60N10/.../40iC60H10/.../40iC60L40iC60L10/.../25NG125N10/.../40NG125L10/.../40Selection guide for 380 / 415 VKBA / KBB trunkingIsc max (kA rms) KBA2510 kA15 kA20 kA25 kACircuit breakeriC60N10/.../25iC60H10/.../25iC60L10/.../25iC60L10/.../25iC60N10/.../25iC60H10/.../25iC60L10/.../25iC60L10/.../25NG125N10/.../25Isc max (kA rms) KBB2510 kA15 kA20 kA25 kACircuit breakeriC60N10/.../25iC60H10/.../25iC60L10/.../25iC60L10/.../25iC60N10/.../25iC60H10/.../25iC60L10/.../25iC60L10/.../25NG125N10/.../25Isc max (kA rms) KBA4010 kA15 kA20 kA25 kA36 kA50 kACircuit breakeriC60N10/.../40iC60H10/.../40iC60L40iC60L10/.../25iC60N10/.../40iC60H10/.../40iC60L40iC60L10/.../25NG125N10/.../40NG125H10/.../40NG125L10/.../40Isc max (kA rms) KBB4010 kA15 kA20 kA25 kA36 kA50 kACircuit breakeriC60N10/.../40iC60H10/.../40iC60L40iC60L10/.../25iC60N10/.../40iC60H10/.../40iC60L40iC60L10/.../25NG125N10/.../40NG125H10/.../40NG125L10/.../40E
52www.se.comDesign guideSelect the right product to support lightingsThe tables below indicate the possible fixing distances in metres. Based on a maximum acceptable deflection of 1/350.Lights are installed continuouslyLights weight per meter (kg)Distance between support D (m)22.533.544.555.560 < W < 3.4KBAKBAKBAKBBKBBKBBKBB3.4 < W < 4.6KBAKBAKBAKBBKBBKBB4.6 < W < 6.7KBAKBAKBBKBBKBB6.7 < W < 9KBAKBAKBBKBB9 < W < 16KBAKBBKBB16 < W < 24KBBKBB24 < W < 30KBBLights are installed between two fixing pointsLights weight (kg)Distance between support D (m)22.533.544.555.560 < W < 11KBAKBAKBAKBBKBBKBBKBBLights are installed next to a fixing pointLights weight (kg)Distance between support D (m)22.533.544.555.560 < W < 11KBAKBAKBAKBBKBBKBBKBBKBBKBBDDDDD
53www.se.comE
54www.se.comApplicationsExamples of lighting managementCar parkLow-level lighting in the parking bays, brighter lighting in traffic areasand full brightness in pedestrian areas.P1EXITP3Factory workshopsDepending on the time slots and zones, ignition strategies, adaptation oflighting levels, lighting scenarios are possible, Canalis DALI or KNX controlsystem connects all luminaries to the controller.WarehousesIn warehouses, dynamic lighting is essential: light is not necessary all the time,everywhere and at the maximum level. Depending on the time slots andzones, ignition strategies, adaptation of lighting levels, lighting scenariosare possible, up to the creation of atmospheres lights that promote thevigilance of workers, especially at night. Canalis DALI or KNX controlsystem connects all luminaries to the controller.
55www.se.comGymnasiumIn large open spaces with a good level of external light, the lighting level can be adjustedby a dimmer control. It is also possible to divide the surface area into halves or thirdsdepending on how the space is used.EXITOpen-plan officeAs and when space is reorganized, it is easy to allocate a new control point for anoffice or put luminaires together to form a group.The Canalis DALI or KNX control system is connected to the BMS. It is possible tocreate scenarios, control, and supervise lighting points and monitor electricityconsumption (see diagram page 61)ApplicationsExamples of lighting managementConvenience storeOne light in three on during delivery periods, fully lit when the shop isopen to the public then lighting lowered again after closing, while theshop is being cleaned. By powering one, two, or three phasesthe brightness level is easily manageable (see diagram page 59)F
56www.se.comSensing functionSwitch functionTime management function12347774Auxiliary: iACTp interference filter5Pushbutton: Odace type6Movement sensor: Argus7Canalis KBATimer: MINsiActpfilterArgusmasterswitch1Protection: 2P iC60N and 1P iC60N circuit-breakers2Contactor: 1-ph iCT3Timer: MINs15ApplicationsExamples of electrical diagrams
57www.se.comApplicationsExamples of electrical diagramsCentralized management function125KNX4DALI31SpaceLYnk2Acti9 Energy meter 3Blinds & Shutters actuator 4Push-Button5Remote 6Presence detector with automatic lighting control 7Push-Button 8Push-Button with temperature control 9Acti9 SmartLink10Switch actuator11Fan-Coil actuator (heating & cooling control)12DALI gateway13Thermal valve drive14Acti9 IP SmartLinkEthernet TCP/IPMetering & breakers status (& load control)Light & Room controlModbusDALIKNX1234678510111213141Feed unit2Clamp3Electronic ballast4Connector: KBC16DCS•••T type5Canalis: KBB option TF9
Lighting in the right place at the right time thanks to pre-cabling and time programmingManaging the lighting of a convenience store or superetteCustomer caseThe manager of a convenience store wants toautomate its lighting system. His store comprises two separate lighting areas: storage and sales.In addition, the lighting must be optimized: one luminaire out of three during delivery, after closing and at cleaning time, while full lighting must be ensured during opening hours.The layout of the shelves in the sales area couldbe reorganized, and the reallocation of luminairesshould be performed with minimum works.Our recommendationThe system chosen is 25 A KBA Canalis busbartrunking, and the luminaires shall be installed directly under Canalis KBA by means of KBA40ZFU fasteners.An Acti9 IHP+ 2c clock combined with contactors ensures lighting scripting, and a manual override control of the lighting will be performed from the electrical switchboard.The alteration of the installation duringreorganization of the shelves will be simplified bythe modularity and extreme ease of assembly anddisassembly of the Canalis components.Benefits• Simplicity and speed of execution: from design to installation, no constraints, "Canalis" adapts to all store configurations.• Attractiveness: the white-colored Canalis components ensure consistency with the colors of the luminaires.• Cost optimization: automation of the installation reduces electricity consumption.• Flexibility: no works required when reorganizing the store or changing the sales area.“This document has no contractual value and Schneider Electric cannot be held liable for its content”.se.com
DiagramDocument Number DEBU036EN ©2023 Schneider Electric. All Rights Reserved.Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companiesSchneider Electric Industries SAS35, rue Joseph Monier - CS 30323F92506 Rueil-Malmaison CedexProducts usedProductFunctionQuantityReferenceCanalis KBA25 A straight element-KBA25ED4303WCanalis KBA25 A power supply box1KBA25ABG4WCanalis KBAFasteners-KBA40ZFUCanalis busbar trunkingTap-off connectors-KBC10DCS101, 201, 301Acti9 iC60NMCB 2P1Depend on ratingActi9 IHP+ 2cProgrammable time switch with 2 output contacts1CCT15553Acti9 iC60NMCB 2P3Depend on ratingActi9 iCT25 A 2P contactor3Depend on ratingSolutionMore about Canalis KBAScan or click on QR codeSpecifications• The decentralized lighting electrical distribution architecture shall be prefabricated.• The lighting layout should possibly be reorganized without altering the electrical installation.• A busbar trunking system should ensure simplification of office rearrangement.se.comFExt1Ext25L42N1IHP+2cNL1L2L3Canalis KBA
Lighting in the right place at the right timeLighting management for an office spaceCustomer caseThe manager of an office space needs to organize the lighting layout. He also wants to achieve energy savings by implementing automatic switching on/off of the lighting according to the presence of people and the level of luminosity.In addition, each office lighting must be switched off automatically after a certain period of time in the absence of people.As the offices are regularly rearranged, the installation must be easy to modif y.Our recommendationThe system chosen is Canalis busbar trunking incorporating a DALI architecture without programming.Automatic lighting is provided by master and slave DALI presence detectors, and adjustment of the constant luminosity level office by office is an integral function of the master Argus detectors.These detectors are fastened directly to the busbar trunking or are simply connected to it according to the layout of the offices.Information is transferred uniformly to all the ballasts connected to the master detector network, and an override control of the lighting is performed by push buttons connected to the (master) DALI detector.* DALI: Digital Addressable Lighting Interface.Benefits• Fewer cables: a single duct incorporates the power and the DALI communication buses for the master and slave Argus detectors and DALI ballast (option T of the KBA product ranges).• Communication between the master and slave Argus devices and override control push buttons uses the power supply conductor (power line carrier).• The prefabricated lighting electricity distribution system allows flexibility of installation for arrangement or rearrangement of space, without altering the electrical structure.• Modification of the installation will be easy thanks to the modularity and extreme ease of assembly and disassembly of the Canalis components.“This document has no contractual value and Schneider Electric cannot be held liable for its content”.se.com
DiagramDocument Number DEBU036EN ©2023 Schneider Electric. All Rights Reserved.Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companiesSchneider Electric Industries SAS35, rue Joseph Monier - CS 30323F92506 Rueil-Malmaison CedexProducts usedProductFunctionQuantityReferenceCanalis busbar trunkingTap-off connectors1KBC16DCB21+KBC16ZT1Canalis busbar trunkingConnectors for Argus master detector1KBC16DCB40+KBC16ZT1Canalis busbar trunkingConnectors for Argus slave detector1KBC10DCB40Canalis KBA40 A straight element (with communication bus)-KBA40ED4303TWCanalis KBA40 A power supply box1KBA40ABG4TWCanalis KBAFasteners-KBA40ZFUActi9 iC60NMCB 1P+N1Depend on ratingSolutionMore about Canalis KBAScan or click on QR codeSpecifications• Decentralized DALI lighting system without programming must be used to control the lighting.• The use of a busbar trunking system should insure simplification of office rearrangement.se.comFCanalis KBAPL PL1LEDElectronic ballastArgus masterArgus slave
Control of energy consumption and easy reallocationLight management of a large office buildingCustomer caseThe facility manager wants to automate the lighting of a large office building, while keeping the possibility of local control, energy consumption management and luminaire maintenance.He also needs to adapt the lighting according to a timer program, the presence of people and the level of natural light based on several areas.In addition, he wants to perform override control of lighting by area, and rapidly reallocate a work area.Our recommendationThe choice to make is a KNX type BuildingManagement System, connected to a "Canalis KBB" busbar trunking architecture with 1 or 2 electrical network, DALI-compatible, performing lighting management, measuring and monitoring.KNX presence detectors located in each area maintain a constant luminosity level in the presence of employees, for optimal working conditions.Override setting of the lighting for each area is performed by KNX switches, and fault information is sent by the ballasts via the DALI communication network.In case of rearrangement, it is easy to allocate new monitoring points for an office or group of luminaires.* DALI: Digital Addressable Lighting Interface.Benefits• Fast installation: Canalis busbar trunking, formed of prefabricated elements, can be installed rapidly and with protection. Connections require no tools and are designed to prevent any risk of incorrect connection.• Flexibility: reallocation of the various offices is made easy.• Simplified maintenance: no preventive maintenance campaign (renewal of the lamps according to their service life).• Efficiency: simple lighting management and cost optimization scenarios.“This document has no contractual value and Schneider Electric cannot be held liable for its content”.se.com
DiagramDocument Number DEBU036EN ©2023 Schneider Electric. All Rights Reserved.Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companiesSchneider Electric Industries SAS35, rue Joseph Monier - CS 30323F92506 Rueil-Malmaison CedexProducts usedProductFunctionQuantityReferenceCanalis KBB40 A straight element (with communication bus)-KBB40ED4303TW, KBB40ED44305TWCanalis KBB40 A power supply box1KBB40ABG4TW, KBB40ABG44TWCanalis busbar trunkingFasteners-KBA40ZFUCanalis busbar trunkingTap-off connectors-KBC16DCB21 + KBC16ZT1KNX Push ButtonPush button1NU553018KNX power supplyPower supply1MTN684064, MTN684032KNX DALI GatewayCommunication gateway1MTN6725-0001KNX ArgusPresence detector3MTN630919Acti9 iC60NMCB 1P+N1Depend on ratingActi9 iC60NMCB 3P+N1Depend on ratingSolutionMore about Canalis KBBScan or click on QR codeSpecifications• The lighting management system has to be a decentralized distribution system incorporating a DALI communication bus connected to the Building Management System. It should perform control of the luminaires by area, and allow the creation of lighting scenarios according to the occupants' hours of presence and the extinguishing of unoccupied areas.• The solution should be based on prefabricated elements with tap-offs, being completely scalable.• The connections should be done without tools.se.comFCanalis KBBArgusArgusKNXLNPower supplyDALILND+D -KNX DALI GatewayLED Electronic ballast
64www.se.comIndexCatalogue numbersCatalogue numbersWeight(kg)PageKBA25ABG4W0.20023, 24, 30KBA25ED2300W2.60024KBA25ED2302W2.40024KBA25ED2303TW2.60034KBA25ED2303W2.60024KBA25ED2305TW2.60034KBA25ED2305W2.60024KBA25ED4202W1.90024, 30KBA25ED4300W2.60024, 30KBA25ED4302W2.40024, 30KBA25ED4303TW2.60032, 34KBA25ED4303W2.60023, 24, 30KBA25ED4305TW2.60032, 34KBA25ED4305W2.60024, 30KBA40ABD4TW0.50032, 34KBA40ABD4W0.50024, 30KBA40ABG4TW0.40032, 34KBA40ABG4W0.40024, 30KBA40ABT4TW0.50032, 34KBA40ABT4W0.50024, 30KBA40AF0.70039KBA40DF405TW1.50032, 34KBA40DF405W1.50024, 30KBA40DF420TW4.50032, 34KBA40DF420W4.50024, 30KBA40ED2203TW1.90034KBA40ED2203W1.90024KBA40ED2300W3.10024KBA40ED2303TW3.10034KBA40ED2303W3.10024KBA40ED2305TW3.10034KBA40ED2305W3.10024KBA40ED4203TW1.90032, 34KBA40ED4203W1.90024, 30KBA40ED4300W3.10024, 30KBA40ED4303TW3.10032, 34KBA40ED4303W3.10024, 30KBA40ED4305TW3.10032, 34KBA40ED4305W3.10024, 30KBA40EDA20W1.60039KBA40ZFG20.20038KBA40ZFPU0.10538KBA40ZFSL0.10538KBA40ZFSU0.05024, 30, 32, 34, 38KBA40ZFU0.10523, 24, 30, 32, 34, 38KBA40ZFU2W0.10538KBB25ED2300W2.40026KBB25ED2303W2.40026KBB25ED4300W2.60026KBB25ED4303W2.60026KBB25ED22300W4.60024KBB25ED22303W4.60024KBB25ED22305TW4.60034KBB25ED22305W4.60024KBB25ED42300W4.70024, 30KBB25ED42305TW4.70032, 34KBB25ED42305W4.70024, 30KBB25ED44300W4.80024KBB25ED44305TW4.80034KBB25ED44305W4.80024KBB40ABD4W0.50026KBB40ABD44TW0.50032, 34KBB40ABG4W0.40026KBB40ABG44T2W0.40034KBB40ABG44TW0.40032, 34KBB40ABG44W0.40024, 30KBB40ABT4W0.40026KBB40ABT44TW0.40032, 34KBB40ABT44W0.50024, 30KBB40AF0.01839KBB40DF405W0.80024, 26KBB40DF420W1.90024, 26KBB40DF4405TW0.80032, 34KBB40DF4405W0.80024, 30Catalogue numbersWeight(kg)PageKBB40DF4420TW1.90032, 34KBB40DF4420W1.90024, 30KBB40ED2202W1.70026KBB40ED2300W2.70026KBB40ED2303W2.70026KBB40ED4202W1.90026KBB40ED4300W3.10026KBB40ED4303W3.10026KBB40ED22203TW3.60034KBB40ED22203W3.60024KBB40ED22300W5.20024KBB40ED22303W5.20024KBB40ED22305TW5.20034KBB40ED22305W5.20024KBB40ED42203TW3.80032, 34KBB40ED42203W3.80024, 30KBB40ED42300W5.70024, 30KBB40ED42305TW5.70032, 34KBB40ED42305W5.70024, 30KBB40ED44203TW3.80034KBB40ED44203W3.80024KBB40ED44300W6.10024KBB40ED44305T2W6.10034KBB40ED44305TW6.10034KBB40ED44305W6.10024KBB40EDA20W1.60039KBB40ZFC0.02038KBB40ZFC50.05038KBB40ZFC60.05038KBB40ZFG10.10038KBB40ZFG20.20038KBB40ZFGU0.00538KBB40ZFL0.05538KBB40ZFMP0.04038KBB40ZFPU0.16038KBB40ZFS230.07038KBB40ZFSL0.03538KBB40ZFSU0.10524, 26, 30, 32, 34, 38KBB40ZFU0.05024, 26, 30, 32, 34, 38KBB40ZFU2W0.10538KBB40ZJ4W0.64039KBB40ZJ44TW0.64039KBB40ZJ44W0.64039KBC10DCB200.06523, 28, 31KBC10DCB400.06528, 31KBC10DCC2110.16528, 31KBC10DCS1010.10028, 31KBC10DCS2010.10028, 31KBC10DCS3010.10028, 31KBC16DCB210.09033, 36KBC16DCB220.09033, 36KBC16DCB230.09028, 31KBC16DCB240.09028, 31KBC16DCB400.09033, 36KBC16DCB410.09028, 31KBC16DCB2160.09029KBC16DCB2260.09029KBC16DCF210.09028, 31, 33, 36KBC16DCF220.09028, 31, 33, 36KBC16DCF400.09028, 31, 33, 36KBC16DCF2160.09029KBC16DCF2260.09029KBC16DCP10.09028, 31, 33, 36KBC16DCP20.09028, 31, 33, 36KBC16DCS101T0.15033, 36KBC16DCS201T0.15033, 36KBC16DCS301T0.15033, 36KBC16ZB10.00539KBC16ZC10.02039KBC16ZL100.00239KBC16ZL200.00239KBC16ZL300.00239KBC16ZT10.01033, 36, 39KFB25CD2531.11538
65www.se.comIndexCatalogue numbersG
66www.se.comNote
67www.se.comNote
Schneider Electric Industries SAS© 2023 - Schneider Electric. All Rights Reserved.All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.35, rue Joseph MonierCS 3032392506 Rueil Malmaison Cedex FranceRCS Nanterre 954 503 439Capital social 896 313 776 €www.se.com06-2023DEBU036EN