www.megger.com 1MFT-X1Multifunction testerDESCRIPTIONThe MFT-X1 new electrical installation testing platform MFT-X1 is the first of a new generation of firmware upgradeable, full functionality multi-function testers for low voltage electrical installations. Intended for use on all low voltage electrical installations including EV charge points and domestic photo-voltaic systems, the range of test capabilities allow for general commissioning of installations and periodic maintenance as well as detailed fault diagnostics.FEATURESTrue Loop™True Loop™ impedance testing is now a standard feature on the MFT-X1. The latest 3-wire non-trip loop testing technology, incorporated with the patented Confidence Meter™, offers an unmatched, reliable, accurate, stable and repeatable loop test solution to the user, allowing testing in the most hostile high noise conditions or close to the source of supply. The technology also removes the risk of RCD uplift whilst reducing typical test times – even on circuits protected by 6 mA or 10 mA protective devices.Patented Confidence meter technologyAll loop impedance ranges are now supported by the Megger patented Confidence meter technology, reducing typical test times for non-trip loop testing to around 7 seconds on quiet circuits, and providing optimised test times for loop impedance testing in difficult noisy supplies. The Confidence meter shows the progress of the loop measurement and indicates the presence of noise on the circuit, removing erroneous values to give a stable and consistent result.MFT-X1 result downloading and CertSuiteTest results can be tagged with circuit data and transferred to CertSuite, the latest cloud base electrical certification software package from Megger.When paired to a mobile device using the low energy Bluetooth® mode, results can be sent directly from the MFT-X1 to an Android or IOS device running Megger CertSuite software. These results are also synchronised with the cloud-based application.With a wide range of certification options, CertSuite is available as a monthly or yearly subscription package for electrical certification of installations taking results directly from the MFT whilst testing. CertSuite is suitable for multiple concurrent users and is optimised for use with the MFT-X1.Results can be stored and reviewed remotely by users whilst on site from different locations, accessed by head office or other users with the relevant permission, with professional looking certification and reports. True Loop™ test with patented Confidence Meter™ CertSuite™ compatible Bluetooth® result transfer Next generation 2-wire and 3-wire non-trip loop testing User upgradeable operating system High resolution 0.001Ω loop test Automatic volt-drop measurement Stabilised insulation test voltage Configurable RCD and EV auto-sequence tests Fast switch rechargeable plug-in battery pack Full colour TFT bonded display Re-designed lead set and carry case solution IP54 operational housing
High resolution loop impedance testingThe MFT-X1 has extended the low end of the loop impedance range from 0.01 ohms to 0.001 ohms resolution and 50 kA current calculation. The True Loop impedance measurement using the patented confidence meter makes these low impedance measurements a realistic option, with two wire test connections and high current testing.RCD custom testingRCD testing can now be optimised with the RCD test configurator. Select a whole suite of tests or only those elements of the RCD you require. You can even add ramp testing to the sequence, optimising and simplifying testing.EV Charge point testingSuitable for both EV charger installation testing with either RCD Type B or RDC protected charge points. The MFT-X1 in conjunction with the Megger EVCA adaptor can test all known EV chargers for installation or maintenance.Stabilised insulation test voltageFor the first time in any multifunction tester, the MFT-X1 incorporates a stabilised insulation test voltage, ensuring output voltage is accurate to within +/-3% +2 digits. This compares to the industry standard of +20% and so provides a more accurate test voltage without the risk of over-voltage damage to circuits or sensitive components.Current measurementThe MFT-X1 uses current clamps for current measurement using the optional Megger MCC1010* current clamp for measurement of AC currents from 1 mA to 1000 A. *Optional accessoryCustomer upgradeable operating systemThe operating system of the MFT-X1 range is upgradable by the user, simply by downloading the latest operating system file (.BIN) from the Megger web site to a suitable microSD card.Insert the updated microSD card and pressing TEST initiates an automatic update process without the need for further user intervention.Display and user interfaceThe user interface utilises the flexibility of the high contrast 480 x 272 colour, TFT bonded display, with a monochrome black on white mode designed specifically for use in difficult lighting conditions.Enhancing the colour coded test selection rotary dial, range selection is now replicated on the instrument screen, ensuring easy use in poor lighting environments. Hot keys for second level functions are clearly shown across the top of each screen and the second control dial provides users with a further quick selection option of any highlighted feature, even if wearing protective gloves.Relevant information is clearly shown on the display, both before and after each test, in full colour, and includes the Confidence Meter™ progress bar, RCD ramp test progress as well as the insulation and continuity measurement bar graph. The new Voltage Widget, displays the L-N, L-E and N-E voltages.Li-ION Battery solutionThe Megger MFT-X1 can be powered by either the Megger Li-ION battery pack or using standard NiMH or Alkaline batteries. The unique 4 Ahr rechargeable Li-ION battery can be swapped with the AA carrier module, providing the fastest and most flexible battery change solution in the industry. APPLICATIONS The primary application is the testing of low voltage electrical installations in domestic, commercial, and industrial installations for single and three phase systems.The wide range of test capabilities extend the use of the MFT-X1 to include: EV charge point testing Domestic PV testing Motor/Generator testing Machine testing Portable appliance safety testing Panel building and switchgear manufacturing Cable testingGraphical assistanceThe instrument has context help to provide graphical circuit connection guidance for each of the measurements.AccessoriesThe MFT-X1 is shipped in a rugged, weather-proof carry case offering outstanding protection and flexible storage. Also included is a complete set of test leads to meet the wide range of connection challenges in modern electrical systems.MFT-X1Multifunction testerwww.megger.com 2
FUNCTIONAL SUMMARYVoltage measurementVoltage range0.001 V to 2 V (mV range) 2 V to 600 V (V range), 1000 V DC (on-CAT rated circuits)Voltage type:Trms, AC, DCPhase sequenceAutomatic phase sequence testing on detection of valid three phase suppliesCurrent measurement (non-contact)AC TrmsUsing optional accessories: MCC1010 current clampMeasurement RangeMCC1010: 1 mA to 300 AContinuity/ResistanceMeasurement range Digital display0.01 Ω to 999 kΩ Auto-ranging Measurement Range Analogue arc0 Ω to 1 MΩ log scaleTest voltage4 V DC to 5 V DCTest current (Nominal)>200 mA 0 Ω >< 2 Ω 10 mA Auto reduction on high resistance (actual current reported in display)Test polaritiesForward polarityBuzzer resistance range> 0.01 Ω < 2 kΩBuzzer threshold0.3, 0.5, 1, 2, 3, 4, 5, 10, 20, 30, 40, 50, 100, 200 ΩInsulation testingMeasurement range Digital display0.001 MΩ to 999 MΩ Auto-ranging Measurement range Analogue arc0.001 MΩ to >1000 MΩ log scaleInsulation test voltages50 V DC to 1000 V DC + Variable 50 V to 999 VTest current1 mA to 2 mAStabilised output voltageOutput test voltage stabilised to -0% +2% +2 VTrue Loop™ loop impedance testing2 Wire – all modesTest typesMode 1: Non-Trip Mode 2: High currentMode 3: High resolutionResolutionNon-Trip: 0.01 ΩHigh current: 0.01 ΩHigh resolution: 0.001 ΩVoltage rangeNon-trip: 48 V AC to 280 V ACHigh current: 48 V AC to 550V ACHigh resolution: 48 V AC to 550 V ACFrequency range45 Hz to 65 Hz (all modes)MFT-X1Multifunction testerwww.megger.com 3
3 Phase testingNon-trip: Single phase onlyHigh current: Three phaseHigh resolution: Three phase3 wire - non-tripTest typesRCD (non-trip) RCD EV (non-trip on 6mA EV RDCs)Resolution0.01 ΩVoltage range48 V AC to 280 VFrequency range45 Hz to 65 Hz3 Phase testingSingle phase onlyVolt dropVolt drop calculationRequires Zref (Ze) and circuit current (I-vdrop)AccuracyDependent on loop impedance accuracyRCD testingRCD types supportedType AC, A, B, AC(S), A(S), B(S)Auto RCD sequence1/2x I∆n, 1x I∆n, 2x I∆n, 5x I∆n, Ramp, 0º/180º (customer configurable)Ramp testing10 mA to 1000 mARDC testing6 mA RDCFault (Touch) voltage0 V to 253 VEarth testing2 wire2 wire earth resistance testMFT-X1Multifunction testerwww.megger.com 4
SPECIFICATIONS Voltage measurementFunction RangeAccuracyVoltage DC0 V ... ±1000 V±1% ± 3 digits Voltage AC/TRMS0 V – 600 V (15 – 500 Hz)±2% ± 1 digitsFrequency15 Hz – 99 Hz 100 Hz – 500 Hz±0.5% ± 2 digit ±2.0% ± 2 digitMillivolt measurementFunction RangeAccuracymV AC/TRMS0 mV to ±1999 mV (50 / 60 Hz)±1% ± 3 digits mV DC0 mV to ±1999 mV±1% ± 3 digitsLive Earth detectionIndicates if the PE terminal is live when selecting the Loop or RCD test ranges. The relevant Loop or RCD test is inhibited. CurrentFunction RangeAccuracyCurrent AC/TRMS0.001 A – 0.100 A±2% ±3 digits0.100 A – 2.000 A±2% ±3 digits2.00 A – 20.00 A±2% ±3 digits20.0 A – 300.0 A±2% ±3 digitsFrequency Bandwidth15 Hz – 500 HzInfluence of Frequency30 Hz – 500 Hz ≤0.25 %Resistance and Continuity FunctionRangeTest CurrentAccuracy200 mA0.01 Ω – 99.9 Ω (0 Ω – 2 Ω) 205 mA ±5 mA±3% ±2 digits10 mA0.01 Ω – 99.9 Ω 10 mA±3% ±2 digits100 Ω – 999 kΩ ±5% ±2 digitsOpen circuit voltage4 V to 5 VEN61557-4 Measurement Range: 0.10 Ω to 999 kΩ.MFT-X1Multifunction testerwww.megger.com 5
Insulation testFunctionRangeAccuracy1000 V0.001 – 999 MΩ±3% ±2 digits500 V0.001 – 500 MΩ±3% ±2 digits> 500 MΩ±10%250 V0.001 – 250 MΩ±3% ±2 digits> 250 MΩ±10%100 V0.001 – 100 MΩ±3% ±2 digits> 100 MΩ±10%50 V0.001 – 50 MΩ±3% ±2 digits> 50 MΩ±10%VAR50 V – 999 VLeakage current > 1 mA±3% ±2 digitsLeakage current < 1 mA±10%Leakage current0.1 μA – 1.99 mA±10%Output voltage-0% +2% +2 V at rated load or lessVoltage display±1% ± 3 VShort circuit current1.5 mA nominalTest current on load1 mA at min pass values of insulationMaximum capacitance2 μF for a stable reading, 5 μF absolute limitEN61557-2 Measurement Range: 0.10 MΩ to 999 MΩ.Loop 2-Wire - No RCD (L-PE, L-N or L-L)FunctionRangeAccuracy2-Wire HR0.001 – 9.999±2% ±0.030 Ω2-Wire0.01 Ω - 9.99 Ω±2% ±5 digits10.0 Ω - 99.9 Ω±10% ±5 digits100 Ω - 1999 Ω±10% ±5 digitsSupply Voltage48 V – 550 VSupply Frequency45 Hz – 65 HzCan be used to measure supply source resistance quickly and reliably between Line and PE or two Live conductors up to 550 V.EN61557-3 Measurement Range: 0.30 Ω to 1999 ΩLoop 2-Wire L-PE with RCD FunctionRangeAccuracy0.01 Ω - 1999 Ω±10% ±5 digitsSupply Voltage48 V – 280 VSupply Frequency45 Hz – 65 HzNote: Uses the Megger Confidence Meter to measure the supply source impedance of circuits protected with an RCD rated ≥30 mA when there are only two connections possible. When a neutral is available the three-wire test will provide a quicker, more accurate result.Note: RCD may trip if there are high leakage currents in the circuit under test. This measurement is immune to the effect of inductance found in some RCDs as it measures resistance (RCD Uplift). EN61557-3 Measurement Range: 1.00 Ω to 1999 ΩMFT-X1Multifunction testerwww.megger.com 6
Loop 3-Wire L-PE with RCDDesignationTest CurrentApplicationRCD15 mAFor circuits protected by an RCD rated <= 30 mARDC EV3 mAFor EV charger circuits protected by a RDC and a Type A RCD rated <= 30 mAFunctionRangeAccuracy0.01 Ω - 9.99 Ω±2% ±5 digits10.0 Ω - 199 9 Ω±10% ±5 digitsSupply Voltage48 V – 280 VSupply Frequency45 Hz – 65 HzNote: Uses the Megger Confidence Meter to measure the supply source impedance of circuits protected with an RCD when three connections are possible. The L-N Loop resistance needs to be less than 12 Ω. The resistances of the L-PE, L-N and N-PE loops are all shown, and the accuracy of the L-PE resistance depends on the maximum resistance displayed. When the neutral is not available the two-wire test must be used. Note: RCD may trip if there are high leakage currents in the circuit under test. This measurement is immune to the effect of inductance found in some RCDs as it measures resistance.EN61557-3 Measurement Range: 1.00 Ω to 1999 ΩRCD TestsTypes A and ACRCD TypesAC, A, AC(S), A(S)RCD Rated Current (IΔn)10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 650 mA, 1000 mA, VAR½ I no-trip Test Current-10% – +0% 0.5 IΔn1 I, 2 I, 5 I trip test – AC current-0% – +10% M • IΔn1 I, 2 I, 5 I trip test – pulsed DC current-0% – +10% 1.4 • M • IΔnTrip time±1% ±1 msRamp trip test current± 5%Fault Voltage (0 V – supply)+5% +15% ±0.5 VSupply Voltage48 V – 280 VSupply Frequency45 Hz – 65 HzType BRCD TypesB, B(S)RCD Rated Current (IΔn)10 mA, 30 mA, 100 mA, 300 mA½ I no-trip Test Current-10% – +0% (0.5 IΔn)1 I, 2 I, 5 I trip test Current-0% – +10% (2 IΔn)Trip time±1% ±1 msTrip current (ramp)± 5%Fault Voltage (0 V – supply)+5% +15% ±0.5 VSupply Voltage48 V – 280 VSupply Frequency45 Hz – 65 HzMFT-X1Multifunction testerwww.megger.com 7
RDC (Type EV) with a 30 mA Type A RCDTest current2.0 mA increasing to 6.3 mA over 2s, before being held at that current for 10s.Trip time±1% ±1 msTrip current (ramp)± 5%Fault Voltage (0 V – supply)+5% +15% ±0.5 VSupply Voltage48 V – 280 VSupply Frequency45 Hz – 65 HzEarthFunctionRangeAccuracy2-Wire test0.01 Ω – 1999 Ω ±2% ±3 digitsTest Frequency128 HzTest Current25 V 4.5 mA / 50 V 450 μAMaximum auxiliary electrode resistance5 kΩ for 25V or 100 kΩ for 50 VNote: The 2-wire earth test measures resistance between the blue and green terminals using a 128 Hz square wave; the result includes the resistance of test leads.EN61557-5 Measurement Range: 1 Ω to 1999 Ω.Power supplyLi-ION rechargeable 9.2 V DC 4400 mAh* (non-serviceable) + charge status indicationAA NiMH9.2 V DC (using an 8xAA carrier and mounting adaptor) *dependent on cells usedAA Alkaline12 V DC (using a 8xAA carrier and mounting adaptor)Battery charger (Li-ion)Input: 110 V/ 230 V AC 50/60Hz 1.3 A Output: 3 A 8.4 V DC Battery LifeLi-ION: 4400 mAh = >16 hrs* *times based on typical daily test profileBattery Charging TimeLi-ION: 2.5 to 3 hrs (ambient temperature dependent)EnvironmentalConditionsRangeOperating Temperature-10 °C to +55 °CStorage Temperature-25 °C to +70 °COperating Humidity90% R.H. at +40 °C maxIngress ProtectionIEC 60529: IP 54 VibrationMIL-PRF-28800F:class 2MechanicalLength 274 mm (10.79 ”)Width96 mm (3.78 ”)Depth143 mm (5.63 ”)Weight – Instrument only1.57 kg (3.46 Ib)Shipping weight5.6 kg (12.35 ib)MFT-X1Multifunction testerwww.megger.com 8
SALES OFFICE Megger LimitedArchcliffe Road DoverCT17 9EN EnglandT. +44 (0) 1304 502101E. UKsales@megger.comMFT-X1_DS_INT_en_V03www.megger.comISO 9001The word ‘Megger’ is a registered trademarkORDERING INFORMATIONDescription Part numberMFT-X1-BS Multifunction tester BS1363 1012-223MFT-X1-SC Multifunction tester Schuko 1012-225MFT-X1-CH Multifunction tester Switzerland 1012-229MFT-X1-AU Multifunction tester AUS/NZ 1012-230 Included accessories Switched test probe SP5 Red test lead, probes, clips and grabbers Blue test lead, probe, clips and grabbers Green test lead, probe, clips and grabbers Li-ION battery 4400 mAh Li-ION battery charge SIA10 MAINS socket interface adaptor UK (boxed)Neck strap Multipurpose hard base carry case Quick start guide Calibration certificate Description Part numberOptional and replacement accessories Multipurpose hard base carry case 1014-985Blow moulded carry case (Polypropylene) 1013-453Switched test probe SP5 1002-774Neck strap replacement 1013-454Li-ION battery 4400 mAh 1013-4508x AA Alkaline quick release battery module with AA cells 1013-452SIA10 MAINS socket interface adaptor UK (boxed) 1014-300SIA20 Mains socket interface adaptor AU 1007-170SIA40 Mains socket interface adaptor SCHUKO 1007-171SIA45 Bipolar Mains socket interface adaptor SCHUKO 1007-158SIA50 Mains socket interface adaptor CH 1007-164SIA60 Mains socket interface adaptor USA 1007-087Li-ION battery charge 1013-4513 lead set RD/GN/BU non-fused (boxed) 1014-2913 lead pro set RD/GN/BU non-fused (boxed) 1014-2923 lead set RD/GN/BU fused 10 A (boxed) 1014-2953 piece grabber set RD/GN/BU (boxed) 1014-2997 piece probe and clip set RD/GN/BU (boxed) 1014-3013 lead RD/GN/BU fused 10 A (boxed) – fused leads only 1014-304MCC1010 Current clamp 1010-516MSA1363 socket adaptor UK 1013-837MTF230 – Schuko (Type-F) Socket adaptor 1013-838LA-KIT Lamp adaptor kit 1014-833UKAS Calibration certificate 1013-460MFT-X1Multifunction tester