www.se.com22PresentationFixing systemsABCDEFFor attachment of the busbar trunking to the structure of the building, either directly or via threaded rods (8 mm diameter), brackets, etc.The fixings are suitable for all types of mounting: on ceilings, suspended, on walls, etc. Regarding fixing installation, some tap-off outlets would not be available.1 Universal fixing bracket For edgewise or flat trunking installation. The recommended fixing distance is three metres for trunking installed edgewise A and 1.5 metres when installed flat B.2 Wall brackets For edgewise mounting only. The recommended fixing distance is two metres.3 Spring fixing bracket These brackets are used to suspend the KN line on threaded rods M8 and do not require tools. The bracket is attached to the treaded rod by the spring mechanism, without nuts or bolts. Adjustment of the length of the threaded rod is simplified and the KN trunking can be installed three times faster. They are suitable for all ratings.4 Pendant Kit The pendant kit includes:• a perforated pendant (length: 1 meter, width: 80 mm) used to suspend a KN line from the bulding structure, an IPN or the ceiling.• a cantilever arm (100 mm) that supports the cable tray under the KN line.• the mounting hardware required to secure the KN bracket and the cantilever arm to the pendant.If neccessary, additional cantilever arms can be ordered.5 Fixing bracket for tracking Designed for fast mounting, it supports the 100 mm cable trays made of perforated sheet-metal or wire mesh. Can be directly installed on Canalis trunking: no addition fixing points required.AB12345DEBU020EN