Canalis KN 40 to 160 ACatalogue 2023Prefabricated busbar trunking for power distributionse.comLine Series
CO2 and P&L impact through... Resource PerformanceGreen Premium brings improved resource efficiency throughout an asset’s lifecycle. This includes efficient use of energy and natural resources, along with the minimization of CO2 emissions.Cost of ownership optimization through... Circular PerformanceWe’re helping our customers optimize the total cost of ownership of their assets. To do this, we provide IoT-enabled solutions, as well as upgrade, repair, retrofit, and remanufacture services.Peace of mind through... Well-being PerformanceGreen Premium products are RoHS and REACh compliant. We’re going beyond regulatory compliance with step-by-step substitution of certain materials and substances from our products.Improved sales through... DifferentiationGreen Premium delivers strong value propositions through third-party labels and services. By collaborating with third-party organizations we can support our customers in meeting their sustainability goals such as green building certifications.Discover what we mean by greenCheck your products!An industry leading portfolio of offers delivering sustainable valueGreen PremiumTMMore than 75% of our product sales offer superior transparency on the material content, regulatory information and environmental impact of our products:• RoHS compliance• REACh substance information• Industry leading # of PEP’s*• Circularity instructions*PEP: Product Environmental Profile (i.e. Environmental Product Declaration)The Green Premium program stands for our commitment to deliver customer valued sustainable performance. It has been upgraded with recognized environmental claims and extended to cover all offers including Products, Services and Solutions.
www.se.com3ABCDEFCatalogue numbers and dimensionsDesign guideApplicationInstallationIndexCanalis KN 40 to 160 APresentationDEBU020EN
www.se.com4A new path for achieving your electrical installations Canalis is part of a comprehensive offer of products that are perfectly coordinated to meet all medium and low voltage electrical distribution requirements. All of these products have been designed to work together: electrical, mechanical and communication compatibility. The electrical installation is thus both optimised and high-performance.Optimum system performance is ensured by coordination between the protection circuit breakers and the busbar trunking used for decentralised distribution.Decentralised electrical distribution with total coordination perfectly satisfies all your requirements in terms of safety, continuity of service, upgradeability and simplicity.Decentralised electrical distribution with total coordination is the ideal solution for a wide range of applications including factories, warehouses, commercial premises, parkings, etc.PresentationCanalis, a comprehensive and consistent busbar trunking system for...ABCDEFDEBU020EN
www.se.com5Easier• CoordinationSchneider Electric pro poses coordinated busbar trunking and circuit breaker combinations for all your applications.For typical applications with power ratings up to 630 kVA, a solution in cluding the low-voltage electrical switchboard, circuit breakers and Canalis busbar trunking en sures an installation sized to handle all short-circuit levels encountered.• DesignThe electrical installation can be designed without knowing the exact loca tion of the equipment to be supplied.• OperationCanalis opens the door to total upgradeability throughout the installation.Connectors with stand ard performance circuit breakers can be in stalled at any point along the busbar trunking run.Safer• Decentralised distribution system The combination of cas cading and discrimination techniques guarantees optimum safety and continuity of service.• DesignTotal discrimination for enhanced protection as standard and at a lower cost.point de la canalisation.• OperationAny changes to your installation are carried out in complete safety.Connectors can be plugged in and out with the trunking live. They are equipped with interlocking systems to pre vent incorrect mounting.Coordination guarantees their installation at any point on the busbar trunking system.Presentation... lighting and power distribution in all types of buildingsABCDEFDEBU020EN
www.se.com6PresentationPanorama of the rangeHorizontal and vertical distribution from 100 to 1000 A - IP55Canalis KS *Aluminium: Copper:690 VPre-lacquered white (RAL9001)3 m, 5 m and additional or customized components3P + N + PE0.5 m or 1 m on each side for horizontal version, and on one side for vertical version16 A to 400 A (plug-in)Units for circuit breakers (modular, Compact NSX), fuses, sockets> Riser ducting offer> Fixing devices with quick adjustment> Cable ducts> Installation accessories> Fire barriers100 A, 160 A, 250 A, 400 A, 500 A, 630 A, 800 A, 1000 A160 A, 250 A, 400 A, 630 A, 800 A* Canalis KS range is available on se.com or catalogue: DEBU026ENHorizontal open track distribution from 250 to 630 A - IP20/42I-Line Track250 A, 400 A, 630 A690 VPre-lacquered white (RAL9003)Standard 3 m or customized3L + N + PEContinuous opened channel16 A to 125 A (plug-in)> Data Center IT room> Fixing devices with quick adjustment> Installation accessories> Color customizationPower distribution from 40 to 160 A - IP55Canalis KN *40 A63 A100 A160 A500 VPre-lacquered white (RAL9001)2 m and 3 m3L + N + PE0.5 m, 1 m on 1 side16 A to 63 A (plug-in)Units for modular circuit breakers, fuses and sockets> Flexible components > Fixing devices with quick adjustment> Remote control bus > Cable ducts> Installation accessories* Canalis KN range is available on se.comPower transmission and distribution from 800 to 6300 A - IP55Canalis KT *Aluminium: Copper:1000 VPre-lacquered white (RAL9001)2 m and 4 m3L + PE 3L + N + PE 3L + N + PER0.5 m or 1 m25 A to 630 A (plug-in)400 A to 1250 A (bolt-on)Units for circuit breakers (modular, Compact NSX), fuses, sockets> Power supply ends > Direction change angles and T-pieces> Fixing devices and fuses800 A, 1000 A, 1250 A, 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A1000 A, 1350 A, 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A, 6300 A* Canalis KT range is available on se.com or catalogue: KTA: ref. DEBU021EN / KTC: ref. DEBU024ENPower transmission for outdoor and harsh environment from 800 to 6300 A - IP68Canalis KR *800 A, 1000 A, 1250 A, 1350 A , 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A, 6300 A1000 VGray (RAL7030)Up to 3 m3L3L + N or 3L + PE or 3L + PEN 3L + N + PE---> Power supply ends > Direction change angles and T-pieces> Fixing devices > Fire resistant elements* Canalis KR range is available on se.com or catalogue ref. DEBU031ENLighting and low power distribution from 25 to 40 A - IP55Canalis KBA25 A40 A690 VPre-lacquered white (RAL9003)2 m and 3 m2 or 4 + PE0.5 m, 1 m on 1 sideL + N + PE or3L + N + PE (10/16 A)pre-cabled or to be cabled,with phase selection or fixed polarity, with lighting control With fuses or without protection> Flexible components > Fixing devices with quick adjustment > Communication bus (DALI, KNX, ASI)> Cable ductsCanalis KBB25 A40 A690 VPre-lacquered white (RAL9003)2 m and 3 mSingle circuit2 or 4 + PEDual circuit2 + 2 + PE2 + 4 + PE4 + 4 + PE0.5 m or 1 m on 1 or 2 sidesL + N + PE or3L + N + PE (10/16 A) pre-cabled or to be cabled,with phase selection or fixed polarity, with lighting control With fuses or without protection> Flexible components > Fixing devices with quick adjustment> Communication bus (DALI, KNX, ASI)> Cable ductsRated service currentRated insulation voltageColorLine componentsBranching pointsAccessoriesIncUiLength of componentsNumber of conductorsCenter to center distanceProtection typeABCDEFDEBU020EN
www.se.com7PresentationPanorama of the rangeHorizontal and vertical distribution from 100 to 1000 A - IP55Canalis KS *Aluminium: Copper:690 VPre-lacquered white (RAL9001)3 m, 5 m and additional or customized components3P + N + PE0.5 m or 1 m on each side for horizontal version, and on one side for vertical version16 A to 400 A (plug-in)Units for circuit breakers (modular, Compact NSX), fuses, sockets> Riser ducting offer> Fixing devices with quick adjustment> Cable ducts> Installation accessories> Fire barriers100 A, 160 A, 250 A, 400 A, 500 A, 630 A, 800 A, 1000 A160 A, 250 A, 400 A, 630 A, 800 A* Canalis KS range is available on se.com or catalogue: DEBU026ENHorizontal open track distribution from 250 to 630 A - IP20/42I-Line Track250 A, 400 A, 630 A690 VPre-lacquered white (RAL9003)Standard 3 m or customized3L + N + PEContinuous opened channel16 A to 125 A (plug-in)> Data Center IT room> Fixing devices with quick adjustment> Installation accessories> Color customizationPower distribution from 40 to 160 A - IP55Canalis KN *40 A63 A100 A160 A500 VPre-lacquered white (RAL9001)2 m and 3 m3L + N + PE0.5 m, 1 m on 1 side16 A to 63 A (plug-in)Units for modular circuit breakers, fuses and sockets> Flexible components > Fixing devices with quick adjustment> Remote control bus > Cable ducts> Installation accessories* Canalis KN range is available on se.comPower transmission and distribution from 800 to 6300 A - IP55Canalis KT *Aluminium: Copper:1000 VPre-lacquered white (RAL9001)2 m and 4 m3L + PE 3L + N + PE 3L + N + PER0.5 m or 1 m25 A to 630 A (plug-in)400 A to 1250 A (bolt-on)Units for circuit breakers (modular, Compact NSX), fuses, sockets> Power supply ends > Direction change angles and T-pieces> Fixing devices and fuses800 A, 1000 A, 1250 A, 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A1000 A, 1350 A, 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A, 6300 A* Canalis KT range is available on se.com or catalogue: KTA: ref. DEBU021EN / KTC: ref. DEBU024ENPower transmission for outdoor and harsh environment from 800 to 6300 A - IP68Canalis KR *800 A, 1000 A, 1250 A, 1350 A , 1600 A, 2000 A, 2500 A, 3200 A, 4000 A, 5000 A, 6300 A1000 VGray (RAL7030)Up to 3 m3L3L + N or 3L + PE or 3L + PEN 3L + N + PE---> Power supply ends > Direction change angles and T-pieces> Fixing devices > Fire resistant elements* Canalis KR range is available on se.com or catalogue ref. DEBU031ENLighting and low power distribution from 25 to 40 A - IP55Canalis KBA25 A40 A690 VPre-lacquered white (RAL9003)2 m and 3 m2 or 4 + PE0.5 m, 1 m on 1 sideL + N + PE or3L + N + PE (10/16 A)pre-cabled or to be cabled,with phase selection or fixed polarity, with lighting control With fuses or without protection> Flexible components > Fixing devices with quick adjustment > Communication bus (DALI, KNX, ASI)> Cable ductsCanalis KBB25 A40 A690 VPre-lacquered white (RAL9003)2 m and 3 mSingle circuit2 or 4 + PEDual circuit2 + 2 + PE2 + 4 + PE4 + 4 + PE0.5 m or 1 m on 1 or 2 sidesL + N + PE or3L + N + PE (10/16 A) pre-cabled or to be cabled,with phase selection or fixed polarity, with lighting control With fuses or without protection> Flexible components > Fixing devices with quick adjustment> Communication bus (DALI, KNX, ASI)> Cable ductsRated service currentRated insulation voltageColorLine componentsBranching pointsAccessoriesIncUiLength of componentsNumber of conductorsCenter to center distanceProtection typeABCDEFDEBU020EN
www.se.com8ABCDEFSchneider Electric offers different distribution systems to fit all your operating needs.The Canalis decentralized distribution concept.PresentationA Canalis installation for every distribution systemDecentralized distributionDecentralized distribution lets you• Design installations without layout details• Upgrade without shutting down production• Get systems up and running sooner thanks to faster installation• Generate savings depending on the number of loads.For manufacturing industries• Mechanical• Textiles• Lumber• Injection moulding• Electronics• Pharmaceuticals• Livestock, etc.Centralized distributionFor all continuous processes• Cement plants• Oil and gas• Petrochemicals• Steel• Paper, etc.Centralized distribution offers• Continuity of service• Combined distribution of power, control and monitoring circuits• Supervision, etc.Upgradeable during operationIn decentralized distribution, evolving operating requirements and costs are integrated right from the start.• The addition, relocation or replacement of load equipment can be carried out quickly, without de-energizing the supply trunking or shutting down operation.• The cost of making such changes is greatly reduced:- loads are located close to supply points- tap-off points are always available- tap-units can be reused or new ones added quickly for load.Relocation or replacement needs.• Reusable in the event of major changes.• When making major modifications to your installation, the existing trunking can be easily dismantled and reused.Combined distributionWhere the advantages of both centralized and decentralized distribution are required.Commercial and service buildings• Offices• Stores• Hospitals• Exhibition halls, etc.Infrastructures• Airports• Telecommunications• Internet data centres• Tunnels, etc.Industrial facilities• Pharmaceuticals• Food processing, etc.DEBU020EN
www.se.com9ABCDEFElectrical power available at all points within the installationPresentationThe Canalis decentralized distribution conceptTotal coordination of the Schneider Electric system provides maximum safety of life and property, continuity of service, upgradeability and ease of installation.Total coordination is made easy by the tables in the "Design Guide". They help you choose the right combination of circuit breakers and busbar trunking.Product characteristics are verified by calculations and tests carried out in our laboratories. Comparative investmentof 400 A electric power system equipment.Exclusive features of the Schneider Electric systemCanalisCable6 CanalisCableCosts (equipment + labor)Number of branching pointsA competitive installationSimplicity, upgradeability, safety and continuity of service and operation.Savings start as soon as the installation begins. With tap-off points every 3 metres, Canalis busbar trunking reduces installation costs.Given the low cost of adding new circuits, savings increase as the number of loads increase, a natural consequence of the growth of your business.DEBU020EN
www.se.com10ABCDEFEasy to installThe compact nature of Canalis makes it easy to integrate in all parts of the building.Since it is based on a decentralized architecture, Canalis can be installed at the same time as the building is being built, which optimizes site construction schedules.Because of the delayed differentiation linked to the Canalis architecture, new constraints can be taken into account without adding to the installation time. Controlling costsThe Canalis ranges are factory-tested, which ensures a very high level of quality on site and considerably improves the success of site acceptance tests.Practical to recycleOver the last 20 years, recycling has become a major challenge for industry. The composition of Canalis ranges guarantees a 95% recycling rate.But the Canalis offers go one better... if a site is being restructured or enlarged, the products can simply be removed and reinstalled in their new environment.Simple to maintain No maintenance is required on the Canalis electrical contacts. The clarity of the Canalis architecture simplifies building maintenance and upgrades: > enlarging office space, > adding check-outs in a supermarket... Decentralized distribution ensures continuity of service; when associated with a 100% maintained or non-maintained supply, the essential functions are guaranteed: > maintaining the cold chain in a hypermarket, > lighting system in a car park...Simple to estimateSimple to maintainPractical to recycleEasy to installSimple to estimateDesigning Canalis installations is straightforward as there is no need to know the exact location, nor the power rating of the loads to be supplied. It is therefore very quick to cost the distribution functions. Moreover, Canalis’s flexibility means you can invest in existing needs without adversely affecting future expansion.Power distribution is a major challenge in the construction and refurbishment of commercial, industrial buildings and data centers.The choice of device is fundamental as it will have an effect on the building’s lifecycle. Infrastructures must comply with existing requirements while being flexible, networked and smart. The Canalis concept is undoubtedly the best solution to meet the needs of today and the challenges of tomorrow.PresentationProduct lifecycleDEBU020EN
www.se.com11ABCDEFDEBU020EN
www.se.com12ABCDEFCanalis®From 100 to 1000 A"Electrical energy available throughoutyour installation."DEBU020EN
www.se.com13ABCDEFDEBU020EN
www.se.com14ABCDEFOur teams are available to provide customers with technical assistance throughout the installation of their projects.Design of electrical distribution architectures: design of decentralized transport and distribution systems technical and financial optimization of busbar trunking design projects transformer / switchboard link installation coordination and discrimination.Full installation drawings*: 3D AutoCAD drawings with corresponding parts lists 2D drawing with dimensions detailed connection drawings*All AutoCADs are available on Traceparts.comBIM Models: will be available on Schneider-electric.com in 2019.Site supervision and commissioning assistance.Training for designers and contractors.Working together on your solutionCanalis Busway "Total Solution":PresentationCanalis tools and servicesAutocad drawingAfter-sales serviceCanBrass drawingProductionTechnical supportProject managementProject launchOn-site instruction and installation12345678DEBU020EN
www.se.com15Quotation and Design toolsCanBrass >is a design and costing tool for Canalis busbar trunking runs.CanCad >is a Plug-in for Autocad. It allows to easily design and get bill of materials.BIMBusway >is a Plug-in for Revit. It allows to easily design and get bill of materials in BIM format.... about Canalis KN on se.com... about Canalis rangesLearn more...PresentationCanalis tools and servicesABCDEFDEBU020EN
www.se.com16PresentationCanalis KN is a comprehensive solutionABCDEF2 Run components3 Changing direction• Rating: 40, 63, 100 and 160 A.• 4 live conductors.• Length: -Basic components: 3 metres, -Additional lengths: 2 and 3 metres.• Changing direction: flexible.1 Feed units and end covers• The feed units delivered with end covers, receive the cables supplying one end or any other point of Canalis KN trunking. (central feed).1452DEBU020EN
www.se.com17ABCDEF4 Fixing system• The fixing system ensures that Canalis KN is well secured, whatever the type of building structure.5 Tap-off units• The tap-off units are used to: -supply loads from 16 to 63 A -or protect nearby loads against overloads due to lightning strikes.• Protection using modular circuit breakers or fuses.43DEBU020EN
www.se.com18PresentationCanalis KN is a fast and easy mounting solutionABCDEFExcellent contactEasy to extendClick!Unmatched upgrading possibilitiesFast installation12Click!Click!DEBU020EN
www.se.com19PresentationCanalis KN is a safe and robust solutionABCDEFAn interlocking device prevents mounting errors and makes it impossible to install or remove an energised tap-off unit.Total safetyThe high degree of protection for Canalis KN means it can be installed in all types of buildings.• IP55 guarantees trunking protection against splashes, dust• IK08 guarantees the strength of the trunking (resistance to shocks)• IPxxD ensures totally safe working conditions for maintenance personnel• Canalis KN complies with sprinkler tests, guaranteeing operation under vertically and horizontally sprayed water for 50 minutes.A high degree of protectionFlexible installationA complete range of tap-off unitsDigital BUSAll components in the KN range are halogen free.In case of fire, Canalis KN releases very small quantities of smoke and no toxic gases..No toxic emission in case of fire+-PENL3L2L1DEBU020EN
www.se.com20PresentationLine componentsABCDEFCanalis KN is designed for low-power distribution. There are two versions:• Canalis KNA: busbar trunking with four live conductors (3L + N + PE), for distribution up to 160 A.• Canalis KNT: identical to KNA, but equipped with a transmission bus with three 2.5 mm2 conductors (except 160 A). This bus can be used to set up simple control/monitoring systems (lighting or other loads).The degree of protection of KNA and KNT trunking is IP55All the insulating and plastic materials are halogen-free and have enhanced fire-withstand capabilities: incandescent wire test as per standard IEC 60695-2 (960°C for components in contact with live parts and 650°C for other components).Feed unitsSupply a Canalis KN line, via a cable. They can be mounted at the end of a line (end feed) or in the middle (central feed). These units are made of moulded plastic for the 40, 63 and 100 A ratings and metal for the 160 A rating. They are equipped with:• terminals for 16 mm2 copper cables on the 63 A feed units, copper contacts for 35 mm2 lugs on the 100 A feed units and for 95 mm2 lugs on the 160 A feed units• multi-diameter knock-outs until 100 A rating and cable-gland plates for the 160 A rating• a 3 x 2.5 mm2 terminal block for connection of the remote-transmission cable (Canalis KNT).Feed units and end covers1121 End feed unitsThey are equipped with a mechanical and electrical locating system (polarisation), making it possible to supply a run from the right or the left. They are supplied with an end cover.2 Central feed unitsThey are supplied with two end covers.TypeCanalis KNACanalis KNTClassic offer without busPENL3L2L1Control system with an internal digital bus+-PENL3L2L1DEBU020EN
www.se.com21PresentationLine componentsABCDEFCarry the current and supply low-power loads. Straight lengths constitute the basic structure of the line and are made up of:1 a carrier casing, crimp closed, made of hot-galvanised sheet steel, pre-lacquered RAL 9001 white. This rail also acts as the protective earth conductor (PE),2 an insulated mounting casing, supporting the live conductors,3 four live aluminium conductors, equipped with silver-plated aluminium/copper bimetal contacts at junctions and tap-off points,4 tap-off outlets with automatic shutters that open and close automatically when tap-off units are installed or removed. They are equipped with blanking plugs to maintain the degree of protection IP55. There are one or two tap-offs per metre, depending on the version,5 a mechanical and electrical jointing system. Electrical connection is via flexible grip contacts made of silver-plated copper. The system ensures automatic and simultaneous connection of all live conductors and the continuity of the protective earth conductor,6 three copper bus conductors (Canalis KNT for the complementary offer).Straight lengthsComponents for changing directionFor changes in direction and detours around obstacles (posts, pipes). They can be shaped by hand, on site, to follow any path.1 Flexible elbow2 Flexible lengthOne metre long, these components can be used in corners to adjust to the lengths of the straight components running along three walls, regardless of the dimensions of the premises.3 3D flexible lengthThree metres long, it can be bent in any direction to avoid major obstacles, particularly useful in false ceilings.Changing direction235412361DEBU020EN
www.se.com22PresentationFixing systemsABCDEFFor attachment of the busbar trunking to the structure of the building, either directly or via threaded rods (8 mm diameter), brackets, etc.The fixings are suitable for all types of mounting: on ceilings, suspended, on walls, etc. Regarding fixing installation, some tap-off outlets would not be available.1 Universal fixing bracket For edgewise or flat trunking installation. The recommended fixing distance is three metres for trunking installed edgewise A and 1.5 metres when installed flat B.2 Wall brackets For edgewise mounting only. The recommended fixing distance is two metres.3 Spring fixing bracket These brackets are used to suspend the KN line on threaded rods M8 and do not require tools. The bracket is attached to the treaded rod by the spring mechanism, without nuts or bolts. Adjustment of the length of the threaded rod is simplified and the KN trunking can be installed three times faster. They are suitable for all ratings.4 Pendant Kit The pendant kit includes:• a perforated pendant (length: 1 meter, width: 80 mm) used to suspend a KN line from the bulding structure, an IPN or the ceiling.• a cantilever arm (100 mm) that supports the cable tray under the KN line.• the mounting hardware required to secure the KN bracket and the cantilever arm to the pendant.If neccessary, additional cantilever arms can be ordered.5 Fixing bracket for tracking Designed for fast mounting, it supports the 100 mm cable trays made of perforated sheet-metal or wire mesh. Can be directly installed on Canalis trunking: no addition fixing points required.AB12345DEBU020EN
www.se.com23PresentationTap-off unitsABCDEFTap-off units with disconnection by unplugging, equipped or not equippedFor rapid connection of loads or secondary lines (e.g. lighting), in compliance with installation standards CEI 60364 and regulations concerning TT, IT and TNS systems.They can be handled under off-load conditions with the trunking energised. All contacts are made of silver-plated copper.Disconnection by unplugging the tap-off unit. Access to the electrical equipment and the terminals is possible only when the tap-off unit is unplugged (i.e. not energised). A safety device prevents connection to the trunking when the cover has been removed.A number of safety devices prevent the operator from:• plugging in the tap-off unit when the cover is closed.• closing the cover before the tap-off unit is locked onto the trunking.• unplugging the tap-off unit when the cover is closed.1 Moulded plastic casing insulating material which is self-extinguishing and halogen free.2 Power socket3 Cover equipped with contact blades4 Trunking locking device (four points)5 Equipment : 5a for fuses 5b for C60 type modular devices6 Cable exit knockoutsAll tap-off units are manufactured in the KNA version (without a remote transmission bus).They can be converted to the KNT version by adding an “Remote control power socket block” KNT63ZT1 (see Accessories page) that must bo erdered separately.225a5b4444116633Tap-off unit disconnection by opening or closing the cover should be carried out only if the downstreamload is de-energisedCategory AC 20 disconnection is obtained by opening the tap-off unit cover. With the cover open, no live parts are accessible. The degree of protection is IPxxB. (protected against access with a finger).DEBU020EN
www.se.com24PresentationTap-off unitsABCDEFSingle-phase tap-off units with phase selection, equipped with a iC60N circuit breakerThey are equipped with a phase selection system (L1, L2 or L3 + N + PE).Positioned as close as possible to the loads; extension leads are not required.1 Tap-off unit with circuit breakerFor protection of the tap-off circuit by a circuit breaker. It is equipped with a Multi 9 single-pole iC60 type circuit breaker.Four-pole tap-off units for modular devices (not equipped)2 Tap-off unit for modular devicesThis tap-off unit accepts most devices available in multiples of 18 mm wide modules:• rated current: 32 A• maximum capacity: 5 modules.Tap-off unit covers can be lead sealed to prevent circuit-breaker switching by unauthorised persons.Tap-off units, with isolators, for modular devices (not equipped)3 Tap-off unit for modular devicesThey can be equipped with modular Multi 9 iC60 type devices. Rated current: 63 A 2 sizes available: 8 or 12 18 mm modules. They are available with windows and blanking plates (devices visible and accessible) or with a plain cover (devices not accessible when energised).Tap-off unit covers can be lead sealed to prevent circuit-breaker switching by unauthorised persons.321DEBU020EN
www.se.com25PresentationTap-off unitsABCDEFTap-off units for power sockets Empty or eqFor the supply of portable loads equipped with household or industrial plugs in a:• garage,• maintenance workshop,• laboratory,• battery charging room, etc.Rated courant: 32 ACapacity: 8 modules in multiple of 18 mm wideTwo versions are available:• pre-equipped with 2 PK or PratiKa power sockets• customisable: -two 90 x 100 mm openings for PK-type (screw connections) or PratiKa (fast and reliable connection without stripping) industrial or household sockets. -direct mounting for industrial IEC 16 A 5P or IEC 32 A 3, 4 or 5P sockets. -mounting on 65 x 85 mm clip-on adapter plate for industrial IEC 16 A 3P or 5P and household 10/16 A 2P + PE sockets.Tap-off unit covers can be lead sealed to prevent circuit-breaker switching by unauthorised persons.Tap-off units with fuse holders (not equipped)For protection of the tap-off by a fuse (not supplied).6 Single-phase tap-off unitCan be equipped with fuse holders for:• NF 8.5 x 31.5 fuse, 16 A maximum, gG and aM type,• BS 88A1 fuse, 20 A maximum.7 Four-pole tap-off unitCan be equipped with fuse holders for:• NF 10 x 38 fuse, 20 A maximum, gG type• NF 10 x 38 fuse, 25 A maximum, aM type• BS 88A1 fuse, 20 A maximum• DIN Neozed E14 fuse, 16 A maximum.8 Tap-off unit with isolatorCan be equipped with fuse holders for:• NF 14 x 51 fuse, gG and aM type 50 A maxi.• BS 88A1 fuse, 30 A• DIN fuse, type Diazed E27 25 A or Diazed E33 50 A or Neozed E18, 50 A.567 - BS / DIN7 - NF8DEBU020EN
www.se.com26PresentationAccessoriesABCDEFAdd-on bus connection blockUsed to tap off the KNT bus.Clips into all tap-offs with isolators and can be used to control the equipment via a bus (BatiBus...).Outlet/tap-off unit interlocking deviceUsed to differentiate and mechanically lock out tap-off units when up to four different Canalis KN lines are present (voltage, frequency, etc.).+-PENL3L2L1DEBU020EN
www.se.com27DEBU020ENABCDEF
www.se.com28Catalogue numbers and dimensionsClassic offerLine componentsStraight lengthsED - Straight horizontal distribution - 3L+N+PE (1) - IP55KNA••ED4•••LengthOutlet nbCatalogue number(mm)FrontRear40 A63 A100 A160 A30006-KNA40ED4306KNA63ED4306KNA100ED4306KNA160ED430630003-KNA40ED4303KNA63ED4303KNA100ED4303KNA160ED430330001-KNA40ED4301KNA63ED4301KNA100ED4301-20004-►KNA63ED4204KNA100ED4204KNA160ED4204► No dedicated reference for this rating. Select the first above available reference.(1) To create a PEN version, a connection is available in each end feed unit.KNA•••ED4306KNA•••ED4303KNA•••ED4301KNA•••ED4204PENL3L2L1Catalogue numberWeight40 A(kg)KNA40ED43065.60KNA40ED43035.60KNA40ED43015.5063 AKNA63ED43065.70KNA63ED43035.70KNA63ED43015.60KNA63ED42044.10100 AKNA100ED43066.70KNA100ED43036.70KNA100ED43016.60KNA100ED42044.80160 AKNA160ED43067.30KNA160ED43037.30KNA160ED42045.20BACDEFDEBU020EN
www.se.com29PENL3L2L1Catalogue numbers and dimensionsClassic offerLine componentsFlexible unitsDF - Flexible length, 1 m for detours around obstacles - IP55KNA•••DF410LengthAngleCatalogue number(mm)40 A63 A100 A160 A100080° to 180°►KNA63DF410KNA100DF410KNA160DF410Additional informationWeight (kg)2.102.102.302.50KNA•••DF410EDF - Flexible length, 3 m for detours around obstacles - IP55KNA100EDF430LengthAngleCatalogue number(mm)40 A63 A100 A160 A100080° to 180°►►KNA100EDF430-Additional informationWeight (kg)--5.00-► No dedicated reference for this rating. Select the first above available reference.KNA100EDF430Minimum curve radiusDL - Flexible elbow for internal or external angle, 80° to 180° - IP55LengthAngleCatalogue number(mm)40 A63 A100 A160 A35080° to 180°►KNA63DL4KNA100DL4KNA160DL4Additional informationWeight (kg)1.201.201.301.50KNA•••DL4KNA•••DL4BACDEFDEBU020EN
www.se.com30Catalogue numbers and dimensionsClassic offerLine componentsEnd feed unitsAB - Cable box feed unit - Right or left mounting - IP55TypeMountingCatalogue number40 A63 A100 A160 AFixedRight or left►KNA63AB4KNA100AB4KNA160AB4Additional informationConnectionTerminals-Lugs (M10 screws)Lugs (M10 screws)Max. Cable size (mm²)max Ø 23 mm-4 x 2404 x 300 or 8 x 120Weight (kg)0.580.581.122.80ABT - Central cable box feed unit - IP55KNA63ABT4TypeMountingCatalogue number40 A63 A100 A160 AFixedRight or left►KNA63ABT4KNA100ABT4KNA160ABT4Additional informationConnectionTerminals-Lugs (M10 screws)Lugs (M10 screws)Max. Cable size (mm²)max Ø 23 mm-4 x 2404 x 300 or 8 x 120Weight (kg)1.471.472.945.50KNA•••AB4KNA•••ABT4Dim.40 to 63 A100 A160 AA265340256B165238258C10010298D71112130E92127185Dim.40 to 63 A100 AA535685B335481C100102D71112E92127► No dedicated reference for this rating. Select the first above available reference.PENL3L2L1KNA63AB4BACDEFDEBU020EN
www.se.com31Catalogue numbers and dimensionsClassic offerLine componentsSpare partsKNA•••ZJ4, KNT•••ZJ4DesignationColourOrder in multiple ofCatalogue numberWeight (kg)For all tap-off unitsOutlet/tap-off unit interlockingdeviceWhite10KNB160ZL100.01Red10KNB160ZL200.01Yellow10KNB160ZL300.01Blue10KNB160ZL400.01DesignationDescriptionCatalogue numberWeight (kg)For tap-off units with modular devicesModular blanking plateDivisible set of 10 x 5139400.08Screw-on plateFor blanking of unused openings131370.10For adapting 65 x 85 mm power-socket bases131360.09Adhesive label (1)Set of 12 label-holders (height 24 mm)089050.50Set of 12 labels (height 24 mm)089030.50Set of 12 divisible labels (height 24 mm)089070.50(1) Self-adhevise support complete with transparent cover and paper label.AccessoriesKNA•••ZJ4, KNT•••ZJ4KNB160ZB1DesignationRating (A)Order in multiple ofCatalogue numberWeight (kg)Spare partsElectrical and mechanical jointing unit40 to 631KNA63ZJ40.60100 to 1601KNA160ZJ40.60IP55 blanking plateAll10KNB160ZB10.02DesignationRating (A)Catalogue numberWeight (kg)Spare parts with built-in transmission busElectrical and mechanical jointing unit40 to 63KNT63ZJ40.60100KNT100ZJ40.60PENL3L2L1KNB160ZL••KNB160ZL10KNB160ZL20KNB160ZL30KNB160ZL40BACDEFDEBU020EN
www.se.com32Catalogue numbers and dimensionsClassic offerFixationsPENL3L2L1KNB160ZF1KNB160ZF2KNB160ZFPUKNB160ZFG100KNB160ZFKP1177,567403016BACDEFFixing system and routing systemDesignationFixing bracketSpring fixing bracketFixing bracketRating (A)40 to 16040 to 16040 to 16040 to 160Max. load (kg)803910011MountingSuspended on M8 threaded rod (1)Wall mounting (2)Suspended on M8 threaded rod (1)Clipped on trunking (3)Order in multiple of1010104Weight (kg)0.1260.0320.260.82Catalogue numberKNB160ZF1KNB160ZF2KNB160ZFPUKNB160ZFG100(1) Maximun recommended distance between fixings: 3 meters.(2) Maximun recommended distance between fixings: 2 meters.(3) Maximun recommended distance between fixings: 1.5 meters.Trunking fixing system DesignationPendant kit (1)Rating (A)40 to 160Max. load (kg)16MountingUnder ceiling or I-beamOrder in multiple of4Weight (kg)1.60Catalogue numberKNB160ZFKP1(1) Maximun recommended distance between fixings: 3 meters.DEBU020EN
www.se.com33PENL3L2L1Catalogue numbers and dimensionsClassic offerTap-off unitsCM - Tap-off units for modular devicesKNB32CM55PolarityCatalogue number32 A3L + N + PEKNB32CM55Number of modules (18 mm)5Weight (kg)0.60Delivered equipped with a DIN rail.For 18 mm modular devices. Cable exitCentre line of tap-off outlets95 (1)(1) Protruding.BACDEFDEBU020EN
www.se.com34Catalogue numbers and dimensionsClassic offerTap-off unitsFor modular devicesPENL3L2L1SM - Tap-off units for modular devicesKNB63SM4••PolarityCatalogue number63 A3L + N + PEKNB63SM48KNB63SM412Number of modules (18 mm)812Max cable size (rigid or flexible)5 x 16 mm²5 x 35 mm²Max cable glands size (not supplied)2 x ISO 502 x ISO 63Weight (kg)2.402.70Disconnection by opening the door.Delivered equipped with a DIN rail.Silver-plated copper terminals (M6) for Copper compression lugs.KNB63SM48X = 432.5 (1)KNB63SM412X = 491Cable exitCentre line of tap-off outlets (1)(1) Protruding.BACDEFDEBU020EN
www.se.com35PENL3L2L1CP - Tap-off units for Pratika Power socketsKNB32CPPolarityCatalogue number32 A3L + N + PEKNB32CPNumber of modules (18 mm)8Weight (kg)2.70Delivered equipped with a DIN rail.For 18 mm modular devices. Centre line of tap-off outlets (1)CP - Tap-off units with power socketsPolarityCurrentVoltagePolarityCatalogue numberWeight (kg)(A)(V)32 A3L + N + PE2Householdsocket Schuko10/162302P+TKNB32CP11D*2.902Householdsocket NF10/162302P+TKNB32CP11F*2.901Householdsocket NF10/162302P+TKNB32CP15F*3.001Industrialsocket164153P+N+T1Householdsocket Schuko10/162302P+TKNB32CP15D*3.001Industrialsocket164153P+N+T1Industrialsocket162302P+TKNB32CP35*3.101Industrialsocket164153P+N+TNumber of modules (18 mm)8* Adaptation for transmission bus (KNT) with remote control power socket block KNT63ZT1 not possible.Centre line of tap-off outlets (1)Catalogue numbers and dimensionsClassic offerTap-off unitsFor modular devices and power sockets(1) Protruding.(1) Protruding.KNB32CP11FKNB32CP15DKNB32CP35BACDEFKNB32CP11DKNB32CP15FDEBU020EN
www.se.com36Catalogue numbers and dimensionsClassic offerTap-off unitsFor NF FusesCF - Tap-off units for cyndrical fuses - P+N with phase selectionKNB16CF2PolarityCatalogue number16 A3L + N + PEKNB16CF2*Number of modules (18 mm)8Max cable size (rigid or flexible)5 x 16 mm²Max cable glands size (not supplied)2 x ISO 50Weight (kg)0.16* Adaptation for transmission bus (KNT) with remote control power socket block KNT63ZT1 not possible.KNB16CF2Cable exitCentre line of tap-off outlets (1)CF/SF- Tap-off units for cynlindrical fuses - 3P+NKNB25CF5PolarityCatalogue number25 A50 A3L + N + PE (1)KNB25CF5*KNB50SF4Number of modules (18 mm)8Max cable size (rigid or flexible)5 x 16 mm²Max cable glands size (not supplied)2 x ISO 50Weight (kg)0.381.50* Adaptation for transmission bus (KNT) with remote control power socket block KNT63ZT1 not possible.KNB25CF5KNB50SF4KNB50SF4 (2) (2)Cable exitCentre line of tap-off outlets(1) Protruding.(1) Also suitable for tap-off unit 3L + PE (N not distributed).(2) Protruding.X = 420PENL3L2L1BACDEFDEBU020EN
www.se.com37Catalogue numbers and dimensionsClassic offerTap-off unitsBS fusesCG - Tap-off units for screew-mounted BS fuses - P+N with phase selectionKNB16CG2PolarityCatalogue number16 A3L + N + PEKNB16CG2*Number of modules (18 mm)8Max cable size (rigid or flexible)5 x 16 mm²Max cable glands size (not supplied)2 x ISO 50Weight (kg)0.16* Adaptation for transmission bus (KNT) with remote control power socket block KNT63ZT1 not possible.KNB16CG2Cable exitCentre line of tap-off outlets (1)CG/SG - Tap-off units for screew-mounted fuses BS - 3P+NKNB20CG5PolarityCatalogue number20 A32 A3L + N + PE (1)KNB20CG5*KNB32SG4Number of modules (18 mm)8Max cable size (rigid or flexible)5 x 16 mm²Max cable glands size (not supplied)2 x ISO 50Weight (kg)0.601.50* Adaptation for transmission bus (KNT) with remote control power socket block KNT63ZT1 not possible.KNB20SG5KNB32SG4KNB32SG4 (2)Cable exitCentre line of tap-off outlets(1) Protruding.(1) Also suitable for tap-off unit 3L + PE (N not distributed).(2) Protruding.PENL3L2L1BACDEFDEBU020EN
www.se.com38Four-pole tap-off unit for screw-type fusesDisconnection by unplugging the tap-off unitKNB16CN5PolarityCatalogue number16 A3L + N + PE (1)3L + PEKNB16CN5*For fuses (not supplied)Néozed E14ConnectionTunnel terminalsMax cable size (flexible / rigid)4 mm² / 6 mm²Max cable glands size (2) (not supplied)ISO 32Weight (kg)0.60* Adaptation for transmission bus (KNT) with remote control power socket block KNT63ZT1 not possible.KNB16CN5Cable exitCentre line of tap-off outlets (3)Tap-off units for screw-type fusesDisconnection by unplugging the tap-off unitKNB••S•4PolarityCatalogue number25 A50 A3L + N + PE (1)3L + PEKNB25SD4KNB50SN4KNB50SD4For fuses (not supplied)Diazed E27Néozed E18Diazed E33ConnectionTunnel terminalsMax cable size (flexible or rigid)16 mm²Max cable glands size (2) (not supplied)ISO 50Weight (kg)1.50KNB••S•4X = 432.5Cable exitCentre line of tap-off outlets (3)(1) Also suitable for tap-off unit 3L + PE (N not distributed).(2) Maximum diameter for a multipolar cable.(3) Protruding.(1) Also suitable for tap-off unit 3L + PE (N not distributed).(2) Maximum diameter for a multipolar cable.(3) Protruding.Catalogue numbers and dimensionsClassic offerTap-off unitsFor Neozed and Diazed fusesPENL3L2L1BACDEFDEBU020EN
www.se.com39Catalogue numbers and dimensionsClassic offerTap-off unitsWith Acti 9 circuit breakerCG - Tap-off units with Acti 9 iC60N circuit breaker - P+N with phase selectionKNB16CM2PolarityCatalogue number16 A3L + N + PEKNB16CM2*KNB16CM2H*Number of modules (18 mm)8Max cable size (rigid or flexible)5 x 16 mm²Max cable glands size (not supplied)2 x ISO 50Weight (kg)0.34* Adaptation for transmission bus (KNT) with remote control power socket block KNT63ZT1 not possible.KNB16CM2 / KNB16CM2H (1)Cable exitCentre line of tap-off outlets(1) Protruding.PENL3L2L1BACDEFDEBU020EN
www.se.com40Catalogue numbers and dimensionsControl systemLine componentsStraight lengthsED - Straight horizontal distribution - 3L+N+PE (1) - IP55KNT••ED4•0•LengthOutlet nbCatalogue number(mm)FrontRear40 A63 A100 A30006-KNT40ED4306KNT63ED4306KNT100ED430630003-KNT40ED4303KNT63ED4303KNT100ED430320004-►KNT63ED4204KNT100ED4204(1) To create a PEN version, a connection is available in each end feed unit.KNT•••ED4306KNT•••ED4303KNT•••ED4204+-PENL3L2L1► No dedicated reference for this rating. Select the first above available reference.Catalogue numberWeight40 A(kg)KNT40ED43065.60KNT40ED43035.6063 AKNT63ED43065.70KNT63ED43035.70KNT63ED42044.10100 AKNT100ED43066.70KNT100ED43036.70KNT100ED42044.80BACDEFDEBU020EN
www.se.com41DL - Flexible elbow for internal or external angle, 80° to 180° - IP55KNT•••DL4LengthAngleCatalogue number(mm)40 A63 A100 A35080° to 180°►KNT63DL4KNT100DL4Additional informationWeight (kg)1.201.201.30DF - Flexible length, 1 m for detours around obstacles - IP55KNT•••DF410LengthAngleCatalogue number(mm)40 A63 A100 A100080° to 180°►KNT63DF410KNT100DF410Additional informationWeight (kg)2.102.102.30KNT•••DL4KNT•••DF410Catalogue numbers and dimensionsControl systemLine componentsFlexible units+-PENL3L2L1► No dedicated reference for this rating. Select the first above available reference.BACDEFDEBU020EN
www.se.com42Catalogue numbers and dimensionsControl systemLine componentsEnd feed unitsAB - Cable box feed unit - Right or left mounting - IP55KNT63AB4TypeMountingCatalogue number40 A63 A100 AFixedRight or left►KNT63AB4KNT100AB4Additional informationConnectionTerminals-Lugs (M10 screws)Max. Cable size (mm²)max Ø 23 mm-4 x 240Weight (kg)0.580.581.12ABT - Central cable box feed unit - IP55KNT63ABT4TypeMountingCatalogue number40 A63 A100 AFixedRight or left►KNT63ABT4KNT100ABT4Additional informationConnectionTerminals-Lugs (M10 screws)Max. Cable size (mm²)max Ø 23 mm-4 x 240Weight (kg)1.471.472.94KNT•••AB4KNT•••ABT4Dim.40 to 63 A100 AA265340B165238C100102D71112E92127Dim.40 to 63 A100 AA535685B335481C100102D71112E92127+-PENL3L2L1► No dedicated reference for this rating. Select the first above available reference.BACDEFDEBU020EN
www.se.com43Catalogue numbers and dimensionsControl systemLine componentsSpare partsKNA•••ZJ4, KNT•••ZJ4AccessoriesKNB160ZL••DesignationColourOrder in multiple ofCatalogue numberWeight (kg)For all tap-off unitsOutlet/tap-off unit interlockingdeviceWhite10KNB160ZL100.01Red10KNB160ZL200.01Yellow10KNB160ZL300.01Blue10KNB160ZL400.01DesignationDescriptionCatalogue numberWeight (kg)For tap-off units with modular devicesModular blanking plateDivisible set of 10 x 5139400.08Screw-on plateFor blanking of unused openings131370.10For adapting 65 x 85 mm power-socket bases131360.09Adhesive label (1)Set of 12 label-holders (height 24 mm)089050.50Set of 12 labels (height 24 mm)089030.50Set of 12 divisible labels (height 24 mm)089070.50(1) Self-adhevise support complete with transparent cover and paper label.AccessoriesKNA•••ZJ4, KNT•••ZJ4KNB160ZB1DesignationRating (A)Order in multiple ofCatalogue numberWeight (kg)Spare partsElectrical and mechanical jointing unit40 to 631KNA63ZJ40.60100 to 1601KNA160ZJ40.60IP55 blanking plateAll10KNB160ZB10.02DesignationRating (A)Catalogue numberWeight (kg)Spare parts with built-in transmission busElectrical and mechanical jointing unit40 to 63KNT63ZJ40.60100KNT100ZJ40.60+-PENL3L2L1KNB160ZL10KNB160ZL20KNB160ZL30KNB160ZL40BACDEFDEBU020EN
www.se.com44Catalogue numbers and dimensionsControl systemTap-off unitsFor modular devicesSM - Tap-off units for modular devicesKNB63SM4••PolarityCatalogue number63 A3L + N + PEKNB63SM48+KNT63ZT1KNB63SM412+KNT63ZT1Number of modules (18 mm)812Max cable size (rigid or flexible)5 x 16 mm²5 x 35 mm²Max cable glands size (not supplied)2 x ISO 502 x ISO 63Weight (kg)2.402.70Disconnection by opening the door.Delivered equipped with a DIN rail.Silver-plated copper terminals (M6) for Copper compression lugs.KNB63SM48X = 432.5 (1)KNB63SM412X = 491Cable exitCentre line of tap-off outlets (1)(1) Protruding.AccessoryKNT63ZT1DesignationOrder in multiple ofCatalogue numberFor tap-off units*Remote control power socket block1KNT63ZT1Weight (kg)0.035(*) KNT63ZT1 is compatible with the following tap-off units:- Four-pole tap-off unit- Tap-off unit with isolator- Tap-off unit with isolator for cylindrical fuses- Tap-off unit with isolator for screw-mounted fuses- Tap-off unit with forscrew-type fuses.+-PENL3L2L1BACDEFDEBU020EN
www.se.com45BACDEFDEBU020EN
www.se.com46Design guideBusbar trunking for low-power distributionCABDEFRun component characteristicsRating of trunking (A)KN4063100160General characteristicsCompliance with standardsIEC/EN 61439-6Degree of protectionIP55555555Mechanical impactsIK08080808Rated current at an ambient temperature of 35 °CIncA4063100160Rated insulation voltageUiV500500500500Rated operational voltageUeV500500500500Rated impulse voltageUimpkV6666Rated frequencyfHz50/6050/6050/6050/60Conductor characteristicsPhase conductorsMean resistance at an ambient temperature of 20 °CR20mΩ/m1.71.71.70.61Mean resistance at Inc and 35 °CR1mΩ/m1.942.052.20.79Mean reactance at Inc, 35 °C and 50 HzX1mΩ/m0.250.250.250.24Mean impedance at Inc, 35 °C and 50 HzZ1mΩ/m1.962.062.230.83Protective conductor (PE)Mean resistance at an ambient temperature of 20 °CmΩ/m1.091.091.091.09Fault loop characteristicsSymmetricalcomponentsmethodPh/Nat 20 °CMean resistanceR0 ph/NmΩ/m6.936.936.932.67Mean reactanceX0 ph/NmΩ/m1.561.561.561.4Mean impedanceZ0 ph/NmΩ/m7.117.117.113.01Ph/PEat 20 °CMean resistanceR0 ph/PEmΩ/m5.155.155.153.34Mean reactanceX0 ph/PEmΩ/m1.681.681.681.29Mean impedanceZ0 ph/PEmΩ/m5.425.425.423.58ImpedancemethodAt 20 °CMeanresistancePh/PhRb0 ph/phmΩ/m3.43.43.41.21Ph/NRb0 ph/NmΩ/m3.43.43.41.24Ph/PERb0 ph/PEmΩ/m2.852.852.851.71For Incat 35 °CMeanresistancePh/PhRb1 ph/phmΩ/m3.894.094.431.58Ph/NRb1 ph/NmΩ/m3.894.094.431.61Ph/PERb1 ph/PEmΩ/m3.143.273.452.22For Incat 35 °C and 50 HzMeanreactancePh/PhXb ph/phmΩ/m0.520.520.520.79Ph/NXb ph/NmΩ/m0.780.780.780.75Ph/PEXb ph/PEmΩ/m0.960.960.960.84Other characteristicsShort-circuit withstand capacityRated peak withstand currentIpkkA6111420Maximum thermal limit I2t (t = 1 s)A2s1.98 x 1061.98 x 1061.98 x 1068 x 106Rated short-time withstand current (t = 1 s)IcwkA1.41.41.42.8Voltage dropComposite voltage drop (hot state) expressed in V / 100 m / A (50 Hz) with the load uniformly distributed over the run. If the load is concentrated at one end of the run, the voltage drop is twice the value indicated in the table.For a power factor of1V/100 m/A0.1680.1780.1910.0680.9V/100 m/A0.1610.1690.1810.0710.8V/100 m/A0.1470.1550.1650.0670.7V/100 m/A0.1330.1400.1490.063This calculation table applies to the three-phase system.To obtain the single-phase voltage drop, the three-phase voltage drop shown above is divided by 0.866. Radiated magnetic fieldRadiated magnetic field strength 1 metre from the trunkingBμT0.0390.0630.1060.186Product selection when harmonics are present (for details, see the "Special Applications" section) Operational current as a function of 3rd harmonic contentTHD y 15 %406310016015 % < THD y 33 %325080130THD > 33 %284063100Permissible current as a function of ambient temperatureAmbient temperature°C< 353540455055Coefficient K1%Sans10.970.940.910.87DEBU020EN
www.se.com47Design guideBusbar trunking for low-power distributionCABDEFTap-off unit characteristicsGeneral characteristicsDegree of protectionIP55Mechanical impactsIK08Rated insulation voltageUiV400, 500 depending on protective deviceRated operational voltageUeV400, 500 depending on protective deviceRated impulse voltageUimpkV4.6Rated frequencyfHz50/60Electrical characteristics of remote control circuit (KNT)Number of conductors3 x 2.5MaterialCopperRated insulation voltageUeV500Rated operational voltageUiV500Rated impulse voltageUimpkV6Rated current at an ambient temperature of 35 °CIncA6Mean resistance at an ambient temperature of 20 °CR20mΩ/m7.6Mean resistance at Inc and 35 °CR1mΩ/m8.7DEBU020EN
www.se.com48Design guideCoordination tables between circuit breaker and Canalis electrical busbar trunkingCABDEFCanalis KNA Ue: 380-415 V ACIsc max. in kA rms10 kA15 kA20 kA25 kA36 kA50 kAType of Canalis busbar trunking KNA40Type of circuit breakeriC60iC60N 40iC60H 40iC60L 40NG125NG125N/H/L 40ComPactNSXmNSXm E/B/F/N/H 40ANSXm B/F/N/H 40AComPact NSXNSX100B/F/N/H/S/L 40AType of Canalis busbar trunking KNA63Type of circuit breakeriC60iC60N 63iC60H 63C120C120N 63C120H 63NG125NG125N/H/L 63NG125H 63NG125L 63ComPactNSXmNSXm E/B/F/N/H 63ANSXm B/F/N/H 63AComPact NSXNSX100B/F/N/H/S/L 63AType of Canalis busbar trunking KNA100Type of circuit breakerC120C120N 100AC120H 100ANG125NG125N/H/L 100NG125H/L 80NG125L 80ComPactNSXmNSXm E/B/F/N/H 100ANSXm B/F/N/H 100AComPact NSXNSX100B/F/N/H/S/LNSX160B/F/N/H/S/LType of Canalis busbar trunking KNA160Type of circuit breakerNG125NG125N125ComPactNSXmNSXm E/B/F/N/H 160NSXm B/F/N/H 160ANSXm F/N/H 160ANSXm N/H 160AComPact NSXNSX100B/F/N/H/S/LNSX160B/F/N/H/S/LNSX250B/F/N/H/S/LNSX100F/N/H/S/LNSX160F/N/H/S/LNSX250F/N/H/S/LNSX100N/H/S/LNSX160N/H/S/LNSX250N/H/S/LDEBU020EN
www.se.com49Simplified design guideDesign of a power distribution line in Canalis busbar trunkingCABDEFExcept in extreme atmospheres, there's no longer any need to hesitate. Canalis can be installed anywhere!"The chronology described below aims to present the steps for the execution of a simple installation. For a detailed study, it is essential to use appropriate tools, certified by the inspection organisations, in accordance with local installation standards. The Ecodial software, published by Schneider Electric, perfectly meets this need".A study grid, enabling you to note your choices and store them, is available on page 52 (to be detached or photocopied).The ambient temperature, presence of dust, condensation water, etc. contribute to the definition of the degree of protection required by the room in which electrical installation will be performed.Canalis KS and KN prefabricated electrical busbar trunking are IP55 by design and can be installed in nearly all premises. See description of the degree of protection (IP) page 54.1 Identify external influencesThe layout of the distribution lines depends on the location of the loads, the location of the power supply source and the mounting possibilities.• A single distribution line serves an area of 4 to 6 metres long.• Load protection id located in the tap-off unit positioned as close as possible to the load.• A single Canalis busbar trunking system powers a series of loads of various capacities.2 Location of loads and trunking installation methodCalculation of the total operating current (In) consumed on a line:In operating = Σ IbIb = current consumed by each loadBUTSince the loads do not all operate at the same time and are not constantly at full capacity, it is necessary to allow for the growth factor or coincidence factor (Ks): In operating = Σ (Ib x Ks).The diversity factor Ks depends on the type and number of loads.3 Power balance: calculation of currents consumed on each distribution lineApplicationNumber of loadsKS factorLighting, heating-1Distribution(Mechanical workshop)2...30.94...50.86...90.710...400.640 and more0.5MOREOVERFor industrial installations, take into account growth in the installed machinery base. A 20% margin is recommended: In operating = Σ Ib x Ks x 1.2.DEBU020EN
www.se.com50Simplified design guide Design of a power distribution line in Canalis busbar trunkingCABDEF4 Choice of canalis trunking corresponding to in operating5 Temperature derating - Calculation of iz: permissible current in trunking6 Derating according to installation method7 Overload protectionBy calculating "In" operating you can determine "In trunking" and hence the trunking to be installed.Select the trunking for which the "In trunking" is directly greater than "In operating".Canalis trunkings are designed to operate in an ambient temperature of 35°C.Above this temperature, the trunking should be derated as per the following table.Canalis KS trunking is designed to be installed edgewise. However, it can also be mounted flat WITHOUT derating.To allow extensions at any time, the prefabricated trunkings are generally protectedat nominal current "In trunking" (or at permissible current Iz if the K1 factor is applied according to the ambient temperature).Depending on the type of protective device adopted, determine the standardisednominal current "In protection" of the overload protection device such that:Choose the equal or immediately lower standardised rating In (protection).Fuses: the typical ratings are given following the series of characteristic numbers of the "Renard" series.Example: 40 - 50 - 63 - 80 - 100 - 125 - 160 - 200, etcCircuit breakers: the typical ratings found at Schneider Electric are, for example:10 - 16 - 20 - 25 - 32 - 40 - 50 - 63 - 80 - 100 - 125 - 160 - 250 - 400 - 630, etc.Finally, confirm the following condition: In standardised protection ≥ In operating.If this is not the case, choose the immediately larger trunking and adjustthe calculations.Example: Canalis KNA 63 A at 45°C: Iz = In trunking x K1 = 63 x 0.94 = 59.22 A.Check that Iz > In operating and check the actual reserve. If necessary, select the next larger trunking.Table 1Total operating current In (A)Trunking40KNA4063KNA63100KNA100 or KSA100160KNA160 or KSA160250KSA250400KSA400500KSA500630KSA630800KSA8001000KSA1000Permissible current according to ambient temperatureIzAmbient temperature< 353540455055K1 factorNone10.970.940.910.87In protection ≤ Iz/K2K2: Factor specific to the type of protective deviceProtection by circuit breaker: K2 = 1Protection by gG/gl fuses: K2 = 1.1DEBU020EN
www.se.com51Simplified design guideDesign of a power distribution line in Canalis busbar trunkingCABDEF8 Verification of voltage drop9 Protection against short circuitsThe voltage drop between the source and any point of use must not exceed the values in the following table:The line-to-line voltage drop, during operation, is indicated in volts per 100 metre per ampere (V/100 m/A), at 50 Hz, with distributed loads on the Canalis line.In the case of a load concentrated at the end of a line, the value of the voltage drop is twice the indicated value.This table applies to the three-phase network. To obtain the single-phase voltagedrop, the three-phase voltage drop shown above is divided by 0.866.Check that the calculated voltage drop is < to the maximum voltage drop wanted.For standard installations with installed capacities of up to 630 kVA, by using the Schneider Electric product offering, the low-voltage electrical switchboard, circuit breakers and even Canalis trunking, your installation can be sized to cope with all levels of short circuits encountered.To verify the correct configuration of your installation (Icc up to 150 kA), refer to the coordination tables page 48.We also invite you to discover Ecodial, our design and computation software dedicated to low-voltage electrical networks (choice of circuit breaker type, calculation of breaking capacity, short-circuit currents, voltage drops, selection of cables, etc.). Ask your Schneider Electric representative about it.Table 2Installation supplied by a distribution networkLightingOther applicationLV public system3%5%High voltage6%8%Table 3For a power factor φ of KN40 A63 A100 A160 A1V/100 m/A0.1680.1780.1910.0680.9V/100 m/A0.1610.1690.1810.0710.8V/100 m/A0.1470.1550.1650.0670.7V/100 m/A0.1330.1400.1490.063DEBU020EN
www.se.com52Simplified design guideDesign of a power distribution line in Canalis busbar trunkingCABDEFMinimum IP of equipment installed in the room:1 Identify external influences2 Location of loads and trunking installation method3 Power balance: calculation of currents consumed on each distribution line5KNA630.84810631.2Canalis busbar trunkingOther solution≤ IP 55≥ IP 55No. of loadsTrunking to be installedTable 1XXXXXXXXXXXXXXX=====Diversity factor KsIn operating (A)Average current Ib (A)In trunking (A)Table 1Reserve factor (e.g. 1.2)Canalis line(s)to be installedCanalis line(s)to be installedRowsRowsEXAMPLEEXAMPLELINE 1LINE 1LINE 2LINE 2LINE 3LINE 3LINE 4LINE 4YOUR INSTALLATIONEXAMPLESpace (m)Space (m)2284 Choice of Canalis trunking corresponding to InRow spacingRow(s) of receivers(m)123From 2 to 6 mReceiversReceiversReceiversReceiversReceiversReceiversCanalis line(s) to be installed112> 6 mReceiversReceiversReceiversReceiversReceiversReceiversCanalis line(s) to be installed123DEBU020EN
www.se.com53Simplified design guideDesign of a power distribution line in Canalis busbar trunkingCABDEF45T° ambient (°c)0.94Derating factor K159.22Iz (A) = In trunking * K1= permissible current*Circuit breakerEXAMPLEEXAMPLELINE 1LINE 1LINE 2LINE 3LINE 4LINE 2LINE 3LINE 45 Temperature derating - Calculation of iz: permissible current in trunking6 Derating according to installation method7 Overload protectionNo derating for Canalis KN placed flat or upright.Trunking protectionTrunking protectionTrunking protectionTrunking protectionTrunking protection Fuses CB* Fuses Fuses Fuses Fuses CB* CB* CB* CB*8 Verification of voltage dropK21.11Iz (A)59.22In protection53.8459.22In standardised of protective device5050 41520.755.326.1510.655%500.90.169Three-phase network voltage (V)XXXXX=====Single-phase loadsSingle-phase loadsSingle-phase loadsSingle-phase loadsSingle-phase loadsConcentrated loadsConcentrated loadsConcentrated loadsConcentrated loadsConcentrated loadsMax. voltage drop (V)Max. voltage drop %Length (m) of Canalis linePower factorVoltage drop (V/100m/A) Tb3Voltage drop (V)(a/100) x b x "In trunking"Voltage drop (V) x 0.866(a)Tb2(b)Voltage drop (V) x 2EXAMPLELINE 1LINE 2LINE 4LINE 39 Protection from short-circuitsRefer to the coordination tables page 48.Check.Check.Check.Check.Check.DEBU020EN
www.se.com54Simplified design guideDetermining the degree of protectionCABDEFStandard IEC 60364-5-51 categorises a large number of external influences to which electrical installations can be subjected, for instance the presence of water, solid objects, shocks, vibrations and corrosive substances.The importance of these influences depends on the installation conditions.For example, the presence of water can vary from a few drops to total immersion.Standard IEC 60529 (February 2001) indicates the degree of protection provided by electrical equipment enclosures against accidental direct contact with live parts and against the ingress of solid foreign objects or water.This standard does not apply to protection against the risk of explosion or conditions such as humidity, corrosive gases, fungi or vermin.The IP code comprises 2 characteristic numerals and may include an additional letter when the actual protection of persons against direct contact with live parts is better than that indicated by the first numeral.The first numeral characterises the protection of the equipment against penetration of solid objects and the protection of people.The second numeral characterises the protection of the equipment againstpenetration of water with harmful effects.Remarks concerning the degree of protection IP• The degree of protection IP must always be read and understood numeral by numeral and not as a whole. For example, an IP31 enclosure is suitable for an environment that requires a minimum degree of protection IP21. However an IP30 wall-mount enclosure is not suitable.• The degrees of protection indicated in this catalogue are valid for the enclosures as presented. However, the indicated degree of protection is guaranteed only when the installation and device mounting are carried out in accordance with professional standard practice.Additional letterProtection of persons against direct contact with live parts.The additional letter is used only if the actual protection of persons is higher than that indicated by the first characteristic numeral of the IP code.If only the protection of persons is of interest, the two characteristic numerals arereplaced by the letter "X", e.g. IPXXB.Degree of protection IPDegree of protection IKStandard IEC 62262 defines a coding system (IK code) indicating the degree of protection provided by electrical equipment enclosures against external mechanical impact.Installation standard IEC 60364 provides a cross-reference between the various degrees of protection and the environmental conditions classification, relating to the selection of equipment according to external factors.IK•• codeThe IK code comprises 2 characteristic numerals (e.g. IK05).Practical guide UTE C 15-103 shows, in the form of tables, the characteristics required for electrical equipment (including minimum degrees of protection), according to the locations in which they are installed.DEBU020EN
www.se.com55Simplified design guideDetermining the degree of protectionCABDEFMeaning of the numerals and letters representing the degree of protection IP1st characteristic numeral: corresponds to protection of equipment against penetration of solid objects and protection of persons against direct contact with live parts.Protection of equipmentProtection of persons00Non-protectedNon-protected11Protected against the penetration of solid objects having a diameter greater than or equal to 50 mm.Protected against direct contact with the back of the hand (accidental contact).22Protected against the penetration of solid objects having a diameter greater than or equal to 12.5 mm.Protected against direct finger contact.33Protected against the penetration of solid objects having a diameter greater than or equal to 2.5 mm.Protected against direct contact with a 2.5 mm diameter tool.44Protected against the penetration of solid objects having a diameter greater than 1 mm.Protected against direct contact with a 1 mm diameter wire.55Dust protected (no harmful deposits).Protected against direct contact with a 1 mm diameter wire.66Dust tight.Protected against directcontact with a 1 mmdiameter wire.2nd characteristic numeral: corresponds to protection of equipment against penetration of water with harmful effectsProtection of equipment0Non-protected1Protected against vertical dripping water (condensation).2Protected against dripping water at an angle of up to 15°.3Protected against rain at an angle of up to 60°.4Protected against splashing water in all directions.5Protected against water jets in all directions.6Protected against powerful jets of water and waves.7Protected against the effects of temporary immersion.8Protected against the effects of prolonged immersion under specified conditions.DEBU020EN
www.se.com56Simplified design guideDetermining the degree of protectionCABDEFDegrees of protection IK against mechanical impactThe IK code comprises 2 characteristic numerals corresponding to a value of impact energy, in joules.Weight (kg)Height (cm)Energy (J)00Non-protected010.207.500.1502100.200317.500.3504250.5005350.70060.5020107402081.703050952010104020Additional letterCorresponds to protection of persons against direct contact with live parts.AWith the back of the hand.BWith the finger.CWith a 2.5 mm diameter tool.DWith a 1.0 mm diameter tool.WeightDEBU020EN
www.se.com57CABDEFDEBU020EN
www.se.com58ApplicationCanalis is adapted for all types of buildingsDABCEFElectrical vehicule Flexibility Scalability Halogen Free Sprinkler proofGarages Flexibility Scalability Cost-effectiveLogistic centers Scalability Cost-effective Digital busHypermarkets Operating continuity Flexibility Scalability Halogen Free Sprinkler proofOffices Flexibility Scalability Halogen FreeCruise ships Halogen Free Sprinkler proof Flexibility CompactKey pointsDEBU020EN
www.se.com59ApplicationCanalis is adapted for all types of buildingsDABCEFData centers Operating continuity Flexibility Scalability Hot pluggabilityWarehouses Flexibility Scalability Cost-effective Halogen Free Sprinkler proofIndustrial Building Evolutivity Cost-effective Halogen FreeLaboratory Evolutivity Hot pluggability Halogen FreeDEBU020EN
www.se.com60EVLink terminal distribution kitSave space and cost in your LV Switchboard:• Installation in half the time in comparison with cables• Better reliability and personal safety• Future readinessDecentralized distribution with Canalis is an optimized solution for indoor car parks / garages, bringing easy servicing and scalability. EVlink terminal distribution kits enable direct connection to the busbar.Decentralized EV chargers electrical distribution with CanalisTM busbar trunking system allows you to save time and cost on installation, and to be ready for future extensions.DEBU020EN
www.se.com61Canalis KN, distribution from 40 to 160 A Technical specificationOffer presentation2-pole and 4-pole pre-assembled and pre-cabled kits for 1 x 8-module tap-off unit •1 x circuit breaker •1 x RCD B-type for electric vehicle applicationsCharging station powerDescription of the kitIncludedkWTap-off unit3.7Protection kit Canalis KN 8 mod. 2P MCB 25 A RCD B EVKNB63SM487.4Protection kit Canalis KN 8 mod. 2P MCB 40 A RCD B EV11Protection kit Canalis KN 8 mod. 4P MCB 25 A RCD B EV22Protection kit Canalis KN 8 mod. 4P MCB 40 A RCD B EVEVLink Terminal Protection Kits featuresCanalis KS, distribution from 100 to 1000 ACharging station powerDescription of the kitIncludedkWTap-off unit3.7Protection kit Canalis KS 8 mod. 2P MCB 25 A RCD B EVKSB63SM487.4Protection kit Canalis KS 8 mod. 2P MCB 40 A RCD B EV11Protection kit Canalis KS 8 mod. 4P MCB 25 A RCD B EV22Protection kit Canalis KS 8 mod. 4P MCB 40 A RCD B EVMCBA9F07440Canalis KS tap-off unitKSB63SM48RCDA9Z51440Electrical distribution architecturesCentralized distributionCanalis distribution (decentralized)EV charger switchboardDEBU020EN
www.se.com62Unload and carry the products inside to an area where they are not exposed to dust or inclement weather.Do not store the busbar trunking outdoors.Take care not to knock or drag the busbar trunking on the ground. That could damage the ends and render connections impossible.Unpack and layout on the floor the trunking components required to mount the first line.Check the position of the feed unit. It must be as close as possible to the switchboard.Drill the holes used to mount the brackets on the wall.Preparation of fixingsCount the number of fixings required to install the trunking components.In this catalogue, you will find a number of fixings suited to different building structures.InstallationEABCDFInstallation of a lineDEBU020EN
www.se.com63Insert fixing plugs in the holes.Position and secure the fixing brackets.Position the Canalis KN trunking in the fixing brackets.Assemble the components.Interconnect the lengths using the mechanical and electrical jointing system.InstallationEABCDFDEBU020EN
www.se.com64Assemble a run component and a component for changing direction.Install a cable duct.In this catalogue, you will find a full range of accessories for running all the adjacent circuits of the installation.Wire the modular devices and then clip in the tap-off unit.In this catalogue, you will find a full range of tap-off units to cover all protection needs using either circuit breakers or fuses.InstallationEABCDFTap-off connectionsDEBU020EN
www.se.com65Industrial power sockets can be simply clipped on.In this catalogue, you will find a full range of power-socket units with household and industrial sockets that are compatible with the entire PK socket range.Last installation step.Connect the supply cable to the Canalis KN feed unit, then to the switchboard.Energise the system to check operation.InstallationEABCDFConnect the feed unit and energiseDEBU020EN
www.se.com66IndexCat. numbersDescriptionPageKNAKNA40ED4301STRAIGHT LENGTH 40 A28KNA40ED4303STRAIGHT LENGTH 40 A28KNA40ED4306STRAIGHT LENGTH 40 A28KNA63AB4END FEED UNIT 63 A30KNA63ABT4CENTER FEED UNIT 63 A30KNA63DF410FLEXIBLES29KNA63DL4FLEXIBLES29KNA63ED4204STRAIGHT LENGTH 63 A28KNA63ED4301STRAIGHT LENGTH 63 A28KNA63ED4303STRAIGHT LENGTH 63 A28KNA63ED4306STRAIGHT LENGTH 63 A28KNA63ZJ4SPARE PART31, 43KNA100AB4END FEED UNIT 100 A30KNA100ABT4FEED UNITS30KNA100DF410FLEXIBLES29KNA100DL4FLEXIBLES29KNA100ED4204STRAIGHT LENGTH 100 A28KNA100ED4301STRAIGHT LENGTH 100 A28KNA100ED4303STRAIGHT LENGTH 100 A28KNA100ED4306STRAIGHT LENGTH 100 A28KNA100EDF430FLEXIBLE UNIT 100 A 3M29KNA160AB4END FEED UNIT 160 A30KNA160ABT4CENTER FEED UNIT 160 A30KNA160DF410FLEXIBLES29KNA160DL4FLEXIBLES29KNA160ED4204STRAIGHT LENGTHS28KNA160ED4303STRAIGHT LENGTH 160 A28KNA160ED4306STRAIGHT LENGTH 160 A28KNA160ZJ4SPARE PART31, 43KNBKNB16CF2TAP OFF UNITS36KNB16CG2TAP OFF UNITS37KNB16CM2TAP OFF UNITS39KNB16CM2HTAP OFF UNITS39KNB16CN5TAP OFF UNITS38KNB20CG5TAP OFF UNITS37KNB25CF5TAP OFF UNIT 25 A FOR NF FUSES36KNB25SD4TAP OFF UNITS38KNB32CM55TAP OFF UNIT 32 A FOR MODULAR EQUIPMENT33KNB32CPTAP OFF UNIT 32 A FOR 2 POWER SOCKETS35KNB32CP11DTAP OFF UNIT 32 A WITH 2 DIN SOCKETS35KNB32CP11FTAP OFF UNIT 32 A WITH 2 NF SOCKETS35KNB32CP15DTAP OFF UNIT 32 A WITH 1 DIN AND 1 IEC SOCK35KNB32CP15FTAP OFF UNIT 32 A WITH 1 NF AND 1 IEC SOCK35KNB32CP35TAP OFF UNIT 32 A WITH 2 IEC SOCKETS35KNB32SG4TAP OFF UNIT 32 A WITH ISOLATOR FOR BS FU37KNB50SD4TAP OFF UNIT 50 A WITH ISOLATOR FOR DIN F38KNB50SF4TAP OFF UNIT 50 A WITH ISOLATOR FOR NF FU36KNB50SN4TAP OFF UNIT 50 A WITH ISOLATOR FOR DIN F38KNB63SM48TAP OFF UNIT 63 A FOR MODULAR EQUIPMENT34, 44KNB63SM412TAP OFF UNIT 63 A FOR MODULAR EQUIPMENT34, 44KNB160ZB1ACCESSORIES31, 43KNB160ZF1FIXATIONS AND SUPPORTS32KNB160ZF2KN FIXING BRACKETS 40 A TO 100 A32KNB160ZFG100BRACKET TRACKING 100 MM32Cat. numbersDescriptionPageKNB160ZFKP1FIXATIONS AND SUPPORTS32KNB160ZFPUSPRING FIXING BRACKET KN32KNB160ZL10TAP OFF LOCATING DEVICE31, 43KNB160ZL20TAP OFF LOCATING DEVICE31, 43KNB160ZL30TAP OFF LOCATING DEVICE31, 43KNB160ZL40TAP OFF LOCATING DEVICE31, 43KNTKNT40ED4303STRAIGHT LENGTHS40KNT40ED4306STRAIGHT LENGTHS40KNT63AB4FEED UNITS42KNT63ABT4FEED UNITS42KNT63DF410FLEXIBLES41KNT63DL4FLEXIBLE ELBOW 63 A41KNT63ED4204STRAIGHT LENGTH 63 A40KNT63ED4303STRAIGHT LENGTH 63 A40KNT63ED4306STRAIGHT LENGTH 63 A40KNT63ZJ4SPARE PART31, 43KNT63ZT1ACCESSORIES44KNT100AB4FEED UNITS42KNT100ABT4FEED UNITS42KNT100DF410FLEXIBLE LENGTH 100 A41KNT100DL4FLEXIBLE LENGTH 100 A41KNT100ED4204STRAIGHT LENGTH 100 A40KNT100ED4303STRAIGHT LENGTHS40KNT100ED4306STRAIGHT LENGTHS40KNT100ZJ4ACCESSORIES31, 43FABCDEDEBU020EN
Schneider Electric Industries SAS© 2023 - Schneider Electric. All Rights Reserved.All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.35, rue Joseph MonierCS 3032392506 Rueil Malmaison Cedex FranceRCS Nanterre 954 503 439Capital social 896 313 776 €www.se.com04-2023DEBU020EN