Arc Guard System – TVOC-2

10 ABB ARC GUARD SYSTEM™ – TVOC-2Optical inputs and outputOptical detectors10 inputs on Arc monitor10 inputs on Extension unit X2 (optional)10 inputs on Extension unit X3 (optional)Current signal from CSU2 inputs: X1.21, X1.22 (optical)Forward current signal to another Arc monitor1 output: X1.23 (optical)Breaker trip contacts (K4, K5, K6)Solid state tripping contacts3 NO solid state type IGBTRated voltage250 V AC / DCMake and carry for 0.2 s30 AMake and carry for 1 s 0.15% duty ration10 ABreaking capacity250 V1.5 AAC-15250 V1 ADC-13110 V3 ADC-1348 V3 ADC13Reinforced insulation between separate contactsVoltage drop 5 V 30 A, 3 V 3 A, 2 V 10 mA Off state current < 1 mA at 250 V 60 Hz Min. recommended load current 10 mASignal relay outputs (K2, K3)Manual or auto resetable2 CO gold-plated contactsRated voltage250 V AC / DCContinous carry Ith5 AMake and carry for 0.2 s30 AMake and carry for 3 s 10% duty ratio15 ABreaking capacity 250 V3 AAC-15250 V0.3 ADC-13110 V0.6 ADC-1348 V2 ADC-13Reinforced insulation between separate contactsIth = 5 A Min switching load: 1 mA at 5 V DC with contacts not used for switching current > 0.5 A if inductive/capacitive load before.Internal Relay Fault (IRF) signal (K1)Self supervision alarm relay1 CO gold-plated contactRated voltage250 V AC/DCContinuous carry, Ith5 AMake and carry for 3 s8 ABreaking capacity 250 V1.5 AAC-15250 V0.15 ADC-13110 V0.3 ADC-1348 V0.5 ADC-13Reinforced insulation between separate contactsIth = 5 A Min switching load: 1 mA at 5 V DC with contacts not used for switching current > 0.5 A if inductive/capacitive load before—Technical data

Previous page: Arc Guard System – TVOC-2 [11 / 20]

Next page: Arc Guard System – TVOC-2 [13 / 20]