1.99EATON CORPORATION CA019040ENProtective DevicesArc Fault Detection Device AFDD+, 2-pole - Technical DataConnection diagram2-pole1234TDIAFDDDimensions (mm)548045104460Tripping Characteristic AFDD+, Characteristics B and CDeclaration AFDD reason for trippingAfter switching on the AFDD is initially a test LED (LED sequence red-yellow-green -> continuous green).Any previous arc tripping reasons are shown only one time after switching on again.Green, no arcing as tripping reason1x yellow, serial arc2x yellow, serial arc of a dimmed load3x yellow, parallel arc4x yellow, over voltage (about 270V) AFDD tripped for self protection5x yellow, overtemperature in the device (about >115°C) AFDD tripped for self protection6x yellow, device error, please check device by an expertThe last AFDD error can be reshown by pressing the test key while the device is switched on.Tripping Characteristic -OL Type 15A, 20A